Page 296 - Practical Power System and Protective Relays Commissioning
P. 296

290  Practical Power System and Protective Relays Commissioning


               Worked example 2





















            FIGURE 19.4.2 Distance protection application setting: Example 2.

               For the following network configuration, the zone 2 setting will be as
            follows for a relay at end A:where  I 2  is called the infeed factor “F”
                                         I 1

                                             I 2
                              Z 2 5 0:85 Z L1 1  3 0:85Z L2
                                             2I 1

                                                I T
                                 Z 2 5 0:85 Z L1 1  Z T
                                                I 1
               In general:
                                 Z 2
                                    $ 1:2-Z 2 5 120% Z L1
                                 Z L1
               t 2 is set to be 0.5 second.
               The setting of zone 3 in general is:

                                  Z 3
                                     $ 1:5 Z 3 5 150% Z L1
                                 Z L1
               t 3 is set to be 0.9 second.
               Final (Backup Step)
               The current starter is used for simple networks where the minimum short
            circuit current is higher than the maximum load currents.
               An impedance starter is more commonly used as this start impedance
            stage should not work in the load area and also should not work for the
            transformer low-voltage faults.
               The lower value of Z st should be chosen.
   291   292   293   294   295   296   297   298   299   300   301