Page 301 - Practical Power System and Protective Relays Commissioning
P. 301

Protection Relays Settings Chapter | 19  295














             FIGURE 19.5.1 Transformer low-impedance differential protection.

                                           1
                                   i 1 5 219  5 0:876 A
                                          250
             where I 1 5 primary current at the HV side of the transformer; i 1 5 secondary
             current at the HV side of the transformer.
                HV correction factor 5  1  5  1  5 1:145
                                   i 1  0:876
                LV side:
                                       25 3 10 3
                                   I 1 5 p ffiffiffi  5 1312 A
                                        3 3 11
                Choose CT ratio 5 1300/1
                                            1
                                  i 2 5 1312   5 1:009A
                                          1300
             where I 2 5 primary current at the LV side of the power transformer;
             i 2 5 secondary current at the LV side of the power transformer.
                                                  1
                             LV correction factor 5  5 0:991
                                                1:009
                For phase correction and zero-sequence current filtering, we use interpos-
             ing CT as follows:
                HV side we use Yy 0 transformer
                LV side we use Yd 11 transformer
             as shown in Fig. 19.5.2.
                Now the current input to the relay is 1 A +0 degree after the interposing
             CT ratio and phase correction at the HV side and the LV side of the power
             transformer.
                Minimum Bias Current
                The maximum voltage is calculated at the low-voltage side.
                                  V max 5 11 3 1:1 5 12:1kV
   296   297   298   299   300   301   302   303   304   305   306