Page 304 - Practical Power System and Protective Relays Commissioning
P. 304

298  Practical Power System and Protective Relays Commissioning


               Tertiary side 11 kV side:
                                    100 3 10 3
                                I 3 5 p  ffiffiffi  5 5248:63 A
                                       3 3 11
               Choose CT 5 5000/1
                                     5248:63
                                 i 3 5       5 1:0497 A
                                       5000
               Tertiary side correction factor 5  1  5 0:952
                                          1:0497
               For phase correction and zero 5 sequence current filtering we use the
            following interposing “auxiliary” transformer for current as follows (refer to
            Fig. 19.5.4):
               HV side: 500 kV Y d11 ICT;
               LV side: 220 kV Y d11 ICT;
               Tertiary side: 11 kV Y y0 ICT.
               Refer to Fig. 19.5.5 for a detailed connection diagram of three-winding
            transformer-biased differential protection.
               Minimum bias current (220 kV side)
               Maximum voltage at the low-voltage side:
                               V max 5 220 kV 3 1:1 5 242 kV

































            FIGURE 19.5.4 Interposing current transformers.
   299   300   301   302   303   304   305   306   307   308   309