Page 302 - Practical Power System and Protective Relays Commissioning
P. 302

296  Practical Power System and Protective Relays Commissioning


















            FIGURE 19.5.2 Interposing transformer in transformer differential protection.



                                      25 3 10 3
                                 I 2 5 p ffiffiffi  5 1193 A
                                       3 3 12:1
                                                 1193
                          I R 5 relay current 5 0:95 3  5 0:871 A
                                                 1300

                       Min Bias  5 2 I Relay set Normal   I Relay at max voltage
                                5 21   0:871Þ 5 0:256
                                    ð
               The minimum voltage is calculated at the low-voltage side.
                                 V min 5 11 3 0:9 5 9:9kV
                                      25 3 10 3
                                  I 2 5 p  ffiffiffi  5 1458 A
                                        3 3 9:9
                                                 1458
                          I R 5 relay current 5 0:95 3  5 1:065 A
                                                 1300

                   Min Bias  5 2 I Relay at min voltage   I Relay set at nominal voltage
                             5 21:065 2 1Þ 5 0:13
                                 ð
               Set the minimum bias at 26%.
               Minimum bias is the highest calculated value of bias at the maximum
            voltage and the minimum voltage at the low-voltage side of the power
            transformer.
               Pickup or I d min set to 10% I n
                                  I d min 5 0:1 3 1 5 0:1A

               First slope bias 5 26%
               Second slope bias 5 80%as shown in Fig. 19.5.3.
   297   298   299   300   301   302   303   304   305   306   307