Page 297 - Practical Power System and Protective Relays Commissioning
P. 297

Protection Relays Settings Chapter | 19  291


                1. Z st # 0.5 Z L min ; this means less than half of the minimum load
             impedance;
                2. Z st $ 1.25 Z 3 .
                t st 5 1.3 second.
                The Compensation Factor (K 0 )










             FIGURE 19.4.3 Distance protection compensation factor (K 0 ) for earth fault measurement.
                The voltage measured by the relay at A is:

                                        0              1
                                                 Z 0 2 Z 1
                                V RA 5 Z 1 I A 1 3I 0  A
                                        @
                                                  3Z 1
                                I R 5 I A 1 K 0 3I 0
                                           0      1
                                             z 0 2 z 1
                                Where K 0 5  @    A
                                              3z 1
                The compensation factor is set in the relay by the values of Z 1 and Z 0 to
             have the correcting value of distance relay measure the line positive imped-
             ance, proportional to its length irrespective of the kind of fault (earth faults
             or phase faults).
                Distance Protection Setting
                Z 1F 5 80% of the protected line;
                Z 2F 5 100% of the protected line 1 50% of the shortest adjacent line;
                Z 3F 5 100% of the protected line 1 125% of the longest adjacent line;
                Z 3R 5 25% of the protected line;
                F 5 forward direction, R 5 reverse direction.

                Worked example 3











             FIGURE 19.4.4 Distance protection application setting: Example 3.
   292   293   294   295   296   297   298   299   300   301   302