Protection Relays Settings Chapter | 19  323


             19.8.2.5 Overload Protection
             Thermal replica relays are used to protect the motor from overloads using a
             separate relay in each phase of the motor. Thermal relays are also used with
             thermal replica relays (resistance temperature detectors embedded in
             machine winding) to give complete protection for the motor.



             19.8.2.6 Low-Voltage Protection
             Undervoltage time delay relay is used as follows:
                V set 5 0.5 V nominal
                Action: Trip after a few seconds.



             19.8.2.7 Phase Rotation Protection
             A negative-phase sequence voltage relay is used.
                v 2 set 5 10% V 2



             19.8.2.8 Phase Unbalance Protection
             Detect I 2 and set as follows:
                I set 5 0.15 I N
                To protect the motor against single-phasing condition:
                 2
                I 2 t 5 40 in general


             19.8.2.9 Out-of-Step Protection for Synchronous Motors

             A relay is used to detect the condition in which the motor draws a heavy
             current in a low-power factor. Therefore, this relay will be a power factor
             relay and will issue a signal to disconnect the field winding and let the motor
             run as an induction motor.



             19.8.2.10 Loss of Excitation Protection for Synchronous Motors
             Undercurrent relay is inserted in a field circuit.