Page 325 - Practical Power System and Protective Relays Commissioning
P. 325

Protection Relays Settings Chapter | 19  319



                Main 1 zone (discriminating zone)—M 1
                R V V range 25 175 V, I RV 5 35 mA, V set 5 130 V
                R I burden 5 3500 Ω, I RV 5 30 mA, R S 5 833 Ω
                R shunt 5 99.23 Ω, Metrosil C 5 450 β 5 0.25 I 5 30 A at 2 seconds.
                Main 2 zone (discriminating zone)—M 2
                R V V range 5 25 175 V, I RV 5 35 mA, V set 5 130 V
                R I burden 5 3500 Ω, I RV 5 30 mA, R S 5 833 Ω
                R shunt 5 99.23 Ω, Metrosil C 5 450, β 5 0.25, I 5 30 A at 2 seconds.
                Check zone (CH)
                R V V range 5 25 175 V, I RV 5 35 mA, V set 5 125 V
                R I burden 5 3500 Ω, I RV 5 30 mA, R S 5 666 Ω
                R shunt 5 96.525 Ω, Metrosil C 5 450, β 5 0.25, I 5 30 A at 2 seconds.


             19.7.3 INTRODUCTION TO BREAKER FAILURE PROTECTION

             This protection is used as backup protection to isolate a fault if the circuit
             breaker of the feeder has a mechanical or other problem preventing it from
             opening the circuit. This protection then isolates all sources which feed the
             fault and also the remote end of the line.


             19.7.4 WORKED EXAMPLE FOR BREAKER FAILURE
             PROTECTION

             CB failure time
                t CB 5 110 180 ms
                Fault clearance time should not exceed 300 ms
                Worked example (Figs. 19.7.5 and 19.7.6):
                Breaker Failure (BF) relay trip logic
                BF relay operating times
                Refer to Fig. 19.7.7 for the breaker failure time and the total fault clear-
             ance time.
                I set BF 5 0.5 I N















             FIGURE 19.7.5 Breaker failure relay connection on an overhead transmission line.
   320   321   322   323   324   325   326   327   328   329   330