Page 320 - Practical Power System and Protective Relays Commissioning
P. 320

314  Practical Power System and Protective Relays Commissioning































            FIGURE 19.7.1 Two-section busbar with two feeders and two incomers.

               R 2 5 0.35 Ω R 5 5 0.36 Ω R 8 5 0.31 Ω
               R 3 5 0.4 Ω R 6 5 0.48 Ω R 9 5 0.33 Ω R 10 5 0.39 Ω
               We use three relays as follows:
               (M 1 ) Discriminating main 1 relay to protect busbar section A1;
               (M 2 ) Discriminating main 2 relay to protect busbar section A2.
               Check zone relay (CH) to protect busbar A1 and A2 to confirm that the
            fault exists on the busbars.
               Relay setting voltage 5  I F
                                  CT  R loop max
               R loop max 5 maximum lead resistance
               Assuming saturation in one CT:
               M 1 (main relay setting)
                              R lead 1  5 2 3 R 1 1 R CT1
                                      5 2 3 0:3 1 2:9 5 3:5 Ω

                              R lead 2  5 2 3 R 2 1 R CT3
                                     5 2 3 0:35 1 2:9 5 3:6 Ω

                              R lead 3  5 2 3 R 3 1 R CT6
                                      5 2 3 0:4 1 3:1 5 3:9 Ω
               R lead max 5 R lead 3 5 3.9 Ω
               Maximum through fault current 5 40 kA
   315   316   317   318   319   320   321   322   323   324   325