Protection Relays Settings Chapter | 19  309















             FIGURE 19.6.2 Loss of excitation impedance protection for generators.
                                              xd  0
                                         X 2 5
                                              2




                Xd 5 191% on 417 MVAb.
                                         Z% MVAb:100
                                   Z ðΩÞ 5
                                             ðVLÞ 2
                                       33 3 417:100
                              Xd ΩðÞ 5            5 28:43 Ω
                                0
                                         100ð22Þ 2
                                     xd 0  28:43
                                 X 2 5  5       5 14:21 Ω
                                      2     2
                X 1 5 xd x 2
                                       191:417 3 100
                               Xd ΩðÞ 5            5 164 Ω
                                         100:ð22Þ 2
                X 1 5 164 14.21 5 150.35 Ω
                X 1 5 150.35 Ω primary, secondary x 1 5 887.065 Ω
                x 2 5 14.21 Ω primary, secondary x 2 5 83.839 Ω

                                                NV
                              t 5 1 second; Z s 5 Z P  5 5:9 Z P
                                                NC
                                      220; 000=O3
                             VT ratio 5          5 2200 5 NV
                                        100=O3
                CT ratio 5 13,000/1 5 NC
                6. Underimpedance protection
                This relay is used as a backup protection for external faults on the high-
             voltage side (220 kV) of a transformer (T 1 ), as shown in Fig. 19.6.3.