Protection Relays Settings Chapter | 19  307

























             FIGURE 19.6.1 Generator and transformer data.


                333 MW xd 5 191% xd 5 33%
                                    0
                Xdv 5 22% F 5 50 Hz
                         2
                I 2 5 15% I .t 5 10 S CT 5 13,000/1 22 kV
                Power Factor (PF) 5 0.8 S 5 417 MVA
                Unit transformer (T 2 )
                25/15/15 MVA 22/6.4/6.4 kV
                Z% 5 8% at 15 MVA
                Generator transformer (T 1 )
                420 MVA 225/22 kV Z% 5 14%
                Station transformer (T 3 )
                25/15/15 MVA
                220/6.4/6.4 kV
                Z% 5 8.2% at 15 MVA
                CTs 5 13,000/1
                1. Stator earth fault protection
                95% stator earth fault relay (R 1 )
                Maximum fault current in neutral 5 20 A
                               1
                I set 5 (1 0.95) 20. 5 0.2 A
                               5
                t to be set to 5 0.05 second.
                Tripping action:
             1. HV CB of transformer T 1 ;
             2. T 2 6.4 kV incoming feeder tripping;
             3. Turbine tripping;
             4. Generator excitation tripping.