308  Practical Power System and Protective Relays Commissioning


               2. 100% stator earth fault protection
               R 2 and R 3 will be two relays as follows:

            1. Undervoltage relay  27 works on third harmonic (R 2 ).
            2. Overvoltage relay (R 3 ) works on fundamental frequency.
               The overlap between 27 and 59 covers 100% of the stator winding.
               3. Stator OC protection
               I set 5 1.05 I N P 5 333 MW then S 5 417 MVA at a power factor of 0.8.

                                     417 3 10 3
                                I N 5         5 10; 943 A
                                     O3 3 22
                                                 1
                                    5 10; 943 3      5 0:842 A
                          I N secondary
                                               13; 000
                          I set     1:05 I N
                                    1:05 3 0:842
                                    5 0:884 A

                                          5 0:9A
                                   SetI set
                                          t 5 6 seconds
               Action: trip of CB of transformer (T 1 ) 220 kV side.
               4. Negative-phase sequence current I 2 protection (46)
               Second stage (trip):
                             I set   5 0:15 I N
                                     5 0:15 3 0:842 5 0:1263 A
                             I set   5 0:127 A
                             Set I set  5 12%
                                 2
                2
               I 2 .t 5 10 where K 5 I 2 .t, K factor 5 10.
               First stage (alarm):
                              Set I alarm 5 0:9 I set  5 0:9 3 0:12
                                               5 0:108
                                               5 10:8%

               Set t alarm 5 3.0 seconds
               Action: trip 220 kV side CB of T 1 second stage.
               Alarm in first stage.
               5. Loss of excitation protection
               Loss of excitation leads to loss of synchronism and running at higher
            than synchronous speed.
               The following impedance relay is used (Fig. 19.6.2).
               X 1 1 x 2 5 xd
               X 1 5 xd x 2
               xd’ 5 33% on 417 MVA base.