312  Practical Power System and Protective Relays Commissioning


               Action:
            1. HV CB tripping of T 1 ;
            2. Incoming of transformer T 2 6.4 kV trip;
            3. Turbine tripping;
            4. Generator excitation tripping.
               10. Generator differential protection
               A biased differential relay is used in the following circumstances
            (Fig. 19.6.4)























            FIGURE 19.6.4 Biased differential protection for generators.

               (I N 5 generator nominal current):
               P 5 O3 V L . I N . cos [
                                        P         333 3 10 3
                             I N  5 p ffiffiffi      5 p ffiffiffi
                                      3V L :cos φ  3V L :cos φ
                                      333 3 10 3
                                  5 p ffiffiffi        5 10; 924 A
                                      3 3 22 3 0:8
                                         10; 924
                             I N secondary 5   5 0:84 A
                                         13; 000

                                     I set 5 0:1 I N
                                        5 0:1 3 0:84
                                         5 0:084 A
               Set bias stop 5 20%
               11. Reverse power protection
               P Reverse set 5 0.01 3 333 5 3.33 MW