Protection Relays Settings Chapter | 19  311


                Relay set 5 47 Hz F 5 50 Hz
                t set 5 4 seconds
                Action:
             1. Trip 220 kV CB. This protection works when load-shedding of the net-
                work does not work.
                8.Overfrequency protection
                Under this condition the unit overspeed and trip are set as follows.
                Relay set 5 54 Hz, F 5 50 Hz
                Action:

             1. Trip of 220 kV CB.
                8. Undervoltage stator protection
                This protection works as a backup for an HV network in two stages.
                Stage 1 has a definite time uv set to 0.7 V n of the generator and trips the
             HV CB.
                Stage 2 trips the unit after 2.5 seconds.
                Stage 1:

                               V set 5 0:7V n 5 0:7 3 100 5 70 V
                t set 5 1.2 second
                Action trip CB of 220 kV transformer (T 1 ).
                Stage 2:
                V set 5 70 V
                t set 5 2.5 seconds
                Action:
             1. Turbine tripping;
             2. Tripping of 6.4 kV transformer incoming;
             3. Generator excitation tripping.
                9. Overvoltage protection
                This protection works when the Automatic Voltage Regulator (AVR)
             maloperates or for manual operation of the excitation system.
                First stage

                                 V set  5 1:1 V n
                                       5 1:1 3 100 5 110 V
                t 5 4.5 seconds
                Action: alarm
                Second stage

                                    V set 5 1:2 V n 5 120 V
                t set 5 3 seconds