304  Practical Power System and Protective Relays Commissioning


            where β 5 0.2 C 5 450
               I 5 30 A
               V metrosil 5 (30) 002 . 450 5 888 V
               So, for CT with 1 A secondary use metrosil with
               C 5 450, β 5 0.2
               I metrosil will be 30 A for 2 seconds
               V metrosil 5 888 V


            19.5.3.2 Worked Example 2 (Fig. 19.5.10)


               Autotransformer 500 MVA 500/220 kV
               HV side CT 1 600/1 R CT1 5 1.5 Ω
               LV side CT 2 1600/1 R CT2 5 2.5 Ω
               Neutral CT 3 1000/1 R CT3 5 2.5 Ω
               Relay stability limit 5 16 I n 5 I through fault
                                          I through fault
                      V s 5 stability voltage 5    3 loop resistance
                                             CT
                                         500 3 10 3
                        V S1 HV side  5 16 3 p ffiffiffi  ð R 1 1 R 2 1 R CT1 Þ
                                           3 3 500
                                     16    500 3 10 3
                                  5     3 p ffiffiffi     ð 2 1 2 1 1:5Þ
                                     600    3 3 500
                                  5 15:396 5:5Þ 5 84:678 V
                                          ð






















            FIGURE 19.5.10 500/220 kV autotransformer 500 MVA protected by high-impedance differ-
            ential protection.