Page 326 - Practical Power System and Protective Relays Commissioning
P. 326

320  Practical Power System and Protective Relays Commissioning









            FIGURE 19.7.6 Breaker failure relay operation logic.













            FIGURE 19.7.7 Breaker failure time and total fault clearance time.

               5 0.5 3 1200 5 600 A
               t CB 5 120 ms
               Action:
               The back trip for all feeders connected on busbar A through busbar
            protection trip relays for the section which this feeder connected to it should
            not exceed 300 ms.
               The remote trip for the breaker is at end B.
               The local retrip for the breaker is at end A.



            Subchapter 19.8


            Motor Protection Setting

            19.8.1 INTRODUCTION

            Here we provide some examples for motor protection settings.


            19.8.2 WORKED EXAMPLES
            19.8.2.1 Motor Faults

            1. Winding faults
            2. Overloading;
            3. Reduced or loss of supply voltage;
            4. Phase reversal;
   321   322   323   324   325   326   327   328   329   330   331