Page 79 - Practical Power System and Protective Relays Commissioning
P. 79

76  Practical Power System and Protective Relays Commissioning


            6.4.6 Verification of Cross Bonding Test of Metallic Sheath of
            Cable

            Cross-bonding is used to reduce the induced currents and eddy currents in
            the metallic sheath. This cross-bonding is made at link boxes. Transposition
            between phases is also made through the cable length. The test is undertaken
            by injecting an AC current of 100 A at the three phases of the cable with the
            other end of phases shorted. Then a measurement of the current passing
            through the cable sheath is made. This current should not exceed 3% of the
            injected current as shown in Fig. 6.10.


            6.4.7 Measurements of Cable Positive Sequence Impedance
            This test can be done by injecting a three-phase power supply on the cable with
            shorting the three-phase conductors of the cable at the remote end of the cable
            as shown in Fig. 6.11.where Z 1 5 Z 2 5 V/I and Z 1 is the positive sequence
            impedance of the cable, Z 2 is the negative sequence impedance of the cable
                                     V           V
                                R 1 5  cosΦ; X 1 5  sinΦ
                                     I            I


            6.4.8 Measurements of Cable Zero Sequence Impedance
            This test can be done by using single phase power supply as shown in
            Fig. 6.12.where Z 0 5 3 V/I and Z 0 is the Zero sequence impedance of the
            cable sequence impedance of
                                     V            V
                               R 0 5 3  cosΦ; X 0 5 3  sinΦ
                                     I             I





















            FIGURE 6.10 Verification of cross-bonding test of metallic sheath of cable.
   74   75   76   77   78   79   80   81   82   83   84