                 Table P7.3 Summary of the process design.
                                           Project name: cooling water system
                 Tower                                          Induced draft water cooling tower
                 Tower model                                          ———————
                 Type                                           concrete, rectangular, counterflow
                                            Design & Operating Conditions
                                  3
                 Circulating water flow, m /hr                             6000

                 Hot(inlet) water temp. C                                  45

                 Cold(outlet) water temp. C                                33

                 Wet-bulb temp. Inlet C                                    29
                 Ambient temp. C                                           –

                 Relative humidity %                                       –
                                                                           3
                                3
                 Makeup water flow, m /hr                            124 (31 m /hr per cell)
                 COC                                                       5
                 Fan                                                    1 per cell,
                                                                             3
                                                            Suction flow rate 218 m /hr, DP ¼ 7 mmWC
                 Fan motor power                                         23.3 HP
                 Number of cells                                        4 in a row
                 Plan area                                              40   10 m
                 Overall tower dimension,                          40,000   10,000   7000
                 L   B   Hmm
                 Water sump dimension, 2 L   B   H mm    40,000   10,000   (1750 water level þ 250 freeboard)
                 Casing material                                       CONCRETE
                 Fill                                               PVC C-19 fill 600 m 3
                 Water distributor                                  Polypropylene nozzles
                                                                     3
                                                                                           2
                 CW pump                                  2 nos   3000 m /hr, discharge pressure 4 kg/cm (g);
                                                                    run by 400 kW motor
                 CW header                                       20 NB ANSI schedule no. 40
                                                                   00



               Further reading
               CTI Code: Tower: Acceptance Test Code for Water-Cooling Towers; Feb, 1990 revision.
               CTI Bulletin TPR-121: The evaluation of Cooling Tower Performance from Field Test Data.