Page 224 - Process Equipment and Plant Design Principles and Practices by Subhabrata Ray Gargi Das
P. 224

222    Chapter 7 Industrial cooling systems




             Summary of available data


                                       3



                              C ¼ 6000 m =hr; T h ¼ 45 C; T c ¼ 33 C; T amb;WBT ¼ 29 C;
                                                               2
                Plant pressure drop in circulating water header ¼ 2 kg/cm
             Tower selection
                                                                                    2
                                                                     2
                                                                                 3
             Water load (L) of CT usually lies between six and seven USG per ft (14.7e17.1 m /m hr)
                                3
                                   2
                Based on L ¼ 15 m /m hr, Tower area ¼ C/L ¼ 6000/15 ¼ 400 m 2
                CT cells are usually square with up to 20 m arms (Refer to Section 7.2.2). In this case, four cells of
             dimension 10   10 m are chosen to provide the tower area.
                This is a moderate size tower and hence, we opt for induced draft design (Refer to Section 7.2.1).
             The cells are placed side by side, with air entry from opposite sides.
                It is also assumed that the circulating water is fairly clean, without much debris getting entrained in
             the flow.
             Fill details
             The fill chosen is “Film Fill” due to its higher contact efficiency compared to “Splash Fill” and “Low
             Clogging Film Fill.” Typically film fill depth varies from 1.2 to 1.5 m (see Table 7.2). Among several
             types of film fills we choose C19 Film Fill with 1.5 m depth. Characteristics of C19 fill with depth
                                      2
             1.5 m under 4 to 7 US GPM/ft water load is given by the equation provided by the manufacturer as
                                          KaV                0:8621
                                              ¼ 2:847  ðL=GÞ
                                            L

             Determination of operating L=G for the fill chosen
             The thermal balance diagram for the tower is based on psychometric data from a standard psycho-
             metric chart (Fig. 7.6). Data relevant to the problem, as derived from the figure, is tabulated in
             Table P7.1. Any intermediate value is found by interpolation.

               Table P7.1 Psychrometric Data for Saturated air at 1000 mbar pressure.
                                           Absolute                    Specific
                                         humidity (kg    Specific      volume of     Enthalpy of
                                                                              3
               Temperature   Aqueous      H 2 O/kg dry  volume of dry  satd air (m /  satd air (kcal/
                                                             3

                  ( C)     Tension (Pa)      air)       air (m /kg)   kg dry air)   kg dry air)
               15             1704          0.011         0.816          0.83         10.263
               20             2337          0.015         0.83           0.85         13.923
               25             3167          0.020         0.844         0.872         18.206
               30             4243          0.027         0.859         0.896         23.732
               35             5623          0.037         0.873         0.924         31.124
               40             7378          0.049         0.887         0.957         39.809
               45             9585          0.065         0.901         0.995         51.005
               50             12,339        0.087         0.915         1.042         66.005
   219   220   221   222   223   224   225   226   227   228   229