Page 259 - Steam Turbines Design, Applications, and Rerating
P. 259

238   Chapter Twelve

            injection pumps presents a great hazard, especially at maximum injec-
            tion rates. To guard against pump failure, untreated boiler feedwater is
            used since these pumps are usually the most reliable in a plant.
              If plant-operating conditions allow, the vacuum on a condensing tur-
            bine should be reduced to 5 to 10 mmHg; for noncondensing turbines,
            the exhaust pressure should be reduced to atmospheric pressure. Note
            that on any noncondensing unit requiring full-speed washing, the
            manufacturer should be consulted about minimum allowable exhaust
            pressure. Extraction turbines should be run with the extraction line
            shut off.
              A steam gauge and thermometer should be installed between the
            trip-throttle valve and the governor-controlled valves. The thermome-
            ter should preferably be a recording type and should be very responsive
            to small changes in temperature.
              Low speed wash, as illustrated in Fig. 12.16, represents a well-
            understood method of deposit removal.
              To start the washing procedure, it is normally recommended to oper-
            ate the turbine on the trip-throttle valve at one-fifth to one-fourth nor-
            mal speed with no load. The live-steam valve to the mixer would now
            be opened and the boiler stop valve closed, after which the trip-throttle
            valve and the governor valves may be opened wide and the speed con-
            trolled by the small live-steam valve to the mixer. Water is then sup-
            plied to the mixing chamber in quantities sufficient to reduce the
            steam temperature at the recommended rate until 10 to 15°F (6 to 9°C)
            superheat at turbine inlet is reached. During the washing cycle the
            exhaust steam should be discharged to the sewer.
























            Figure 12.16 Schematic of low-speed water wash system. (Dresser-Rand Company,
            Wellsville, N.Y.)
   254   255   256   257   258   259   260   261   262   263   264