Page 164 - Thermal Hydraulics Aspects of Liquid Metal Cooled Nuclear Reactors
P. 164

136                   Thermal Hydraulics Aspects of Liquid Metal Cooled Nuclear Reactors

         During the draining sequence, the gas in the drain tank will be pressurized, which can
         be vented or fed back to the top of the facility to equalize the pressure. Drain piping
         sizes and drain tank vent tubing sizes will affect the time for the facility to drain, so
         these should be considered if specific drain target times are required.
            An automated/emergency draining sequence could be initiated by several criteria.
         Typical criteria are listed in Table 3.4.2.
            The choice of valve failure position should be determined considering the type of
         experiments to be performed and the frequency of expected failures, that is, loss of
         power and loss of pressurized air supply. For long-term experiments that may be jeop-
         ardized by any sudden draining sequences, fail-close valves could be more suitable.
         Such fail-close valves could still be actuated at a later stage if necessary, by
         implementing a backup air receiver supply for pneumatic actuated valves and an
         uninterruptible power supply (UPS) for solenoid actuated valves.
            Early Russian experience with LBE facilities suggests avoiding draining (and
         opening) of experimental LBE facilities to avoid oxide and impurity contamination
         of the facility. Never draining an experimental LBE facility is not entirely practical
         for most research institutions or facilities. In any case, allowing solidification inside
         the loop will result in crystallization of impurities on the walls of the facility. It is pref-
         erable that the crystallization of impurities occurs inside the drain tank. In addition,
         not opening the facility to replace components or test sections is also most likely
         unavoidable, and so, procedures should be established to minimize the ingress of oxy-
         gen during shutdown and maintenance. Operational procedures should dictate that the
         facility is always under an inert atmosphere (argon gas preferably) when the loop is
         empty, regardless of whether the facility is hot or cold. When components, instrumen-
         tation, or test sections are replaced, a slight argon overpressure in the facility will
         reduce the amount of oxygen ingress. Foresee valves or install blind flanges where
         test sections are expected to be frequently manipulated or removed.
            The consequences of draining an LBE facility are more difficult to keep under con-
         trol. Recent experience from the COMPLOT facility at SCK CEN has shown the
                                                            l
         potential consequence that draining (and opening) an LBE facility can have on exper-
         imental measurements. Fig. 3.4.4 shows three experimental curves of differential
         pressure drop as a function of flow rate, for the same component (a mock-up fuel
         assembly in this case), on different occasions.





          Table 3.4.2 Typical examples of possible emergency drain criteria

          Criteria          Detection                     Cause
          Low LBE           Two or more thermocouples below  Heat tracing failure/
          temperature       TAL (150°C)                   overcooling
          Low LBE level     Upper level LAL               LBE leak
          Loss of cover gas  Cover gas pressure below threshold  Depressurization of
          pressure                                        expansion tank
   159   160   161   162   163   164   165   166   167   168   169