Rotary UPS Systems
                                                       Rotary UPS Systems  171


                            AUTOBYPASS








                                         CHOKE
                            STATIC
                            SWITCH


                            ~             =

                                =            ~
                          RECTIFIER     INVERTER      UNIBLOCK












            Figure 6.2 UPS employing rotating transformer system.

            system, neither affecting the operation of the other. Thus, the critical
            load will give the same performance as shown in Fig. 6.2.
              The Uniblock system in Fig. 6.2 is also available using the water-
            cooling system of the building thus reducing the system size and air-
            conditioning load and allowing the system to be situated in some unusual
            areas.
              Parallel redundancy is available and a typical circuit is illustrated in
            Fig. 6.4—in this case with static switches between the various paral-
            leling systems adjacent to the loads.


            Generator/Clutch/Machine
            There are available a number of rotary systems employing diesel/clutch
            configurations and we detail their operation below.
              Our first example of close coupled diesel/clutch/generator is provided
            by the system illustrated in Fig. 6.5 as produced by Eurodiesels Ltd.
            Under normal mains operation power fed into the machine rotates the
            synchronous machine at 1125 rpm. Coupled to this machine is the field


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.