Page 250 - Uninterruptible Power Supplies
P. 250

Some System Failures: The Light of Experience!
            248   Chapter Ten


            An Unstable Power Supply
            This incident occurred at a remote location supplied from an overhead
            line connected to a diesel engine generating station. The equipment of
            interest was a rotary-type of UPS in which the synchronous machine
            was supplied with power from a line commutated inverter. On two occa-
            sions a fault on the overhead line was followed by a commutation fail-
            ure within the equipment. It was important to find an explanation for
            the commutation failures and a reconstruction of the sequence of
            events follows.
              The overhead line failures would have been phase-to-phase or phase-
            to-earth faults probably caused by bird strikes. The supply voltage
            would have been severely depressed and at that time several dynamic
            features would have come into play:

            ■ Energy would have been drawn from the UPS flywheel for a few
              tenths of a second until the battery contactor had closed, the rotor
              speed is therefore reduced leading to a low output frequency.
            ■ When the battery contactor closed, the inverter would immediately
              go into current limit in order to accelerate the rotor and correct the
              low frequency.
            ■ The generating station voltage regulator would have increased exci-
              tation in an attempt to restore the voltage.

              As a result of these dynamic features, when the fault was finally
            cleared the supply voltage from the overhead line suddenly increased
            to 118 percent of nominal and this voltage was applied to the line com-
            mutated inverter already in current limit. Commutation was not pos-
            sible and the failure led to a short circuit of the dc supply and a
            complete failure of the UPS output.
              The equipment included a rectifier contactor, and to prevent a
            recurrence the control circuit was changed to ensure that on a loss of
            supply the contactor opened and remained open for 2 s. The equip-
            ment was quite capable of accepting the 118 percent voltage surge
            under normal conditions and the short delay ensured that on restora-
            tion of supply the inverter would have come out of its current-limited
            mode of operation.
              This incident demonstrates the complexity of the occasional failures
            experienced on systems. It is not always easy to reconstruct the events
            leading to a catastrophic failure. After this incident the fault conditions
            were reproduced within the manufacturer’s works to demonstrate that
            the reconstruction was credible.





         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   245   246   247   248   249   250   251   252   253   254