Standby Power Generating Sets
            34   Chapter One


              The openings should be protected by a wire mesh to prevent the
            entry of birds or other wild life; if the mesh is on the outside of the lou-
            vers, birds are prevented from nesting and, if the openings are at street
            level, persons passing by are prevented from depositing litter within
            them.
              The pressure drops across the inlet and outlet louvers must be taken
            into account when calculating the fan duties, if acoustic louvers are fit-
            ted the pressure drops will be higher and the effect on the fan duties
            will be greater.


            Exhaust Systems
            Gas Turbines
            It has already been stated that the layout of gas turbines is constrained
            by the design of the air inlet and exhaust outlet arrangements. Gas tur-
            bines discharge their exhaust to atmosphere; there is no system of
            exhaust pipework and silencers as there is with diesel engines. The
            requirements of the Clean Air Act do not apply to gas turbines, which
            require special consideration by the local authority.
              For these reasons the remainder of this section applies only to diesel
            engine exhaust systems.


            Within the Diesel Engine Room
            Pipe work will be fixed within the engine room to carry the exhaust
            gases from the engine outlet flange, through the wall or ceiling, to the
            outside of the building. The pipe work is fixed to the building structure,
            either from hangers fixed to the walls or ceiling or supported from the
            floor; to allow for the inevitable movement of the engine on its vibra-
            tion dampers, a flexible section of pipe is provided between the engine
            outlet flange and the fixed pipe work. Where the pipe passes through
            walls or ceilings, precautions should be taken to avoid cracking of the
            structure due to heat and vibration. A sleeve or wall plates with clear-
            ance holes should be considered.
              The exhaust gas temperature at the engine outlet will be of the order
            of 600°C and the exhaust pipe work will be subject to thermal expan-
            sion. Expansion is usually permitted by incorporating stainless steel
            bellows type couplings in pipe runs. Wherever the pipe is within reach
            of personnel, inside or outside of the engine room, it is a source of dan-
            ger and must be thermally insulated to reduce the surface temperature
            to a safe value. To reduce the heat radiated within the engine room the
            entire internal exhaust system may be thermally lagged, this also
            reduces the noise transmitted to the room. Both these features make
            the working environment more tolerable.