Page 212 - Water Loss Control
P. 212
Mean Registration at Various Flow Rates: (Designated as Percent of Registration) High Medium 100 93 98 95.2 102 99 102 96.5 103 99 505 482.7 101 96.54
Test Date Low 89 Oct 2004 70 Oct 2004 95 Oct 2004 98 Oct 2004 98 Oct 2004 450 90
Manufacturer Sensus Sensus Sparling Sparling Hersey
Date of Installation June 1991 June 1993 July 1980 Sept 1977 May 1966 Sum of mean registrations……………………………………………………......................... Mean registration for five meters tested…………………………………….......................... Meter Test Data for Large Meters for County Water Company
Meter Type Turbine Turbine Displacement Compound Propeller
Size (in) 3 3 4 6 6
Meter ID Number XYZ001 X00ZAA NB123 NB456 AA002 Source: Ref. 1 TABLE 12.7
185