Page 217 - Water Loss Control
P. 217

190    Cha pte r  T w e l v e


                    however, in the majority of situations, on-site testing is more economical in terms of
                    time and resources. From a technical standpoint, the piping configuration surrounding
                    the meter can have an appreciable impact on the meter’s accuracy, and such impacts
                    can be detected and evaluated when the testing is conducted on-site.
                                                     Both on-site and test bench testing of large
                                                  meters rely on a large volume of water being passed
                     On-site testing of large     through the meter being tested. When tested on a
                     meters is often the preferred   test bench in the shop, water is passed into a tank of
                                                  known volume. In conducting on-site testing, the
                     method as the customer site
                                                  flow registered by the meter being tested is com-
                     is tested for suitability as well
                                                  pared to a meter that has been previously calibrated
                     as the meter for accuracy.
                                                  and known to be accurate. The two meters are con-
                                                  nected in series, and the test water is discharged to
                    waste. Since the calibrated meter is not 100% accurate on all flows, it may be necessary
                    to adjust for its accuracy variance at different rates of flow, in order to ensure proper test
                    results. One very important point to remember in field-testing is that both meters must
                    be full of water and under positive pressure with all air removed. The control valve for
                    regulating flow, therefore, should always be on the discharge side of the calibrated meter.
                    A valve on the inlet side of the meter being tested or one located between two meters for
                    controlling rates of flow should not be used, as inaccurate results may occur.
                       One acceptable method of maintaining proper performance for certain types of
                    larger meters is to replace the operating components and assemblies while leaving the
                    meter body in place. For such meters it is also recommended that an on-site meter accu-
                    racy test be conducted at the time of installation to confirm that the composite metering
                    unit is functioning as designed. If the measurement and registration functions are
                    within one integral assembly, no accuracy tests are required at the time of installation,
                    and the entire unit must be tested at the regular maintenance intervals.
                       Some larger meters have built-in test plugs while others do not. For installations
                    requiring test outlets, these can be fabricated in a number of ways. Service saddles
                    and reducing tees are the most frequently used approaches. These need to be installed
                    according to the recommendations of the meter manufacturer and located so that the
                    connecting hose to the on-site tester is correctly located downstream to the meter. To
                    facilitate periodic testing of the meter, it is suggested that, as part of the original
                    installation process, a short length of pipe be permanently attached to the test outlet,
                    along with a shut-off valve, which can be locked into position. These features will
                    allow for quick, efficient testing at regular intervals throughout the life of the large
                    meter.
                       The piping configuration around the meter must include valves to positively isolate
                    the meter, while still maintaining an adequate flow to the end user through temporary
                    or permanent bypass piping. If either of the isolation valves fails to seal tightly, an inac-
                    curate test result may occur. Similarly, if leakage occurs at either of the valves or at the
                    meter connections, the integrity of the accuracy test may be compromised. The lower
                    the test flow rate, the higher the significance of any such leaks.
                       Large meter settings are relatively expensive and require considerable preliminary
                    planning. These meters are heavy and removal of the meters for servicing or testing is
                    costly and time-consuming. Therefore on-site testing of large meters is the preferred
                    method in many instances. When small meters are rotated out of service, the water
                    supply to the customer property is halted for the typically brief period of time that is
                    needed to remove the old meter and install the new meter. Such outages are usually
   212   213   214   215   216   217   218   219   220   221   222