170                                                                               Boiler Operator’s Handbook

               Back Pressure Control Valves                         cycling on and off on the low-pressure switch because
                    If the system has various loads back pressure con-  there is inadequate refrigerant in the system. It’s readi-
               trol valves can be used to maintain a higher saturation  ly resolved by adding refrigerant but doing so requires
               pressure in evaporators that do not maintain freezing  that EPA license and you may need to bring in a licensed
               temperatures. That prevents the need for defrosting  technician to do it. Checking for spots of oil that are in-
               those evaporators. Back pressure control valves are also  dicative of a refrigerant leak before calling that techni-
               used in temperature sensitive applications where the  cian can help you reduce the cost of his services because
               product being cooled is damaged by colder tempera-   he’ll know the extent of work necessary if you spot a
               tures. Back pressure control valves simply restrict the  leak. A leak means a considerable amount of work has
               flow of gas (vapor) from the evaporator to keep the pres-  to be done to return the system to normal.
               sure, and therefore the related saturation temperature,   A high pressure switch is normally connected to
               above the preset minimum value. The throttling device  the hot gas line near the compressor discharge.  You
               controls the flow of refrigerant independent of the back  may hear this referred to as a high head pressure switch
               pressure control valve. I’ve had to reset the valves sev-  because they normally sense the pressure at the com-
               eral times with changes in cargo.                    pressor head. In systems with multiple compressors
                                                                    you will normally find a combination high and low gas
               Limit and Operating Controls                         pressure switch mounted at each compressor with con-
                    Loss of refrigerant, accidental crimping of tubing, a  nections inside each compressor’s isolating valves for
               dirty condenser, an iced up evaporator, and loss of con-  exclusive control of  that compressor. One  purpose  of
               denser air or cooling water flow can result in damage to  the high-pressure switch is to shut down the compres-
               the equipment, especially the compressor. Limit controls  sor before the motor is overloaded. The high-pressure
               are provided on systems to prevent damage to equip-  switch should always be set at a value equal to or lower
               ment in the system by shutting down the compressor  than the maximum design pressure of the compressor
               whenever operating pressures or temperatures exceed  discharge, hot gas piping, condenser, and liquid line. A
               preset limits. These devices are either mounted at strate-  high-pressure switch also prevents accidental operation
               gic locations in the system or are incorporated in remote  continuing when a discharge isolating valve is closed—
               sensors wired to the system controls. You can think of  just in case you forgot to open it. Regardless, you should
               each of them as a device operating a simple switch that  make a habit of checking to ensure the valves are open
               turns a compressor on or off. Process refrigeration may  before trying to start the compressor. It’s a bit difficult
               include other devices not listed here and you should, I’ll  with packed valves because you have to remove the
               say it again, read the instruction manual so you under-  caps but my experience tells me it’s always advisable
               stand their purpose and operation.                   to check, especially if you’re not the only one operating
                    The most common limit device is a low-pressure  that equipment. The combination high and low pressure
               switch which is connected near the outlet of the evapo-  switch also shuts down the compressor when you forget
               rator and opens an electrical circuit when the pressure  to open the suction isolating valve.
               in the evaporator falls below the switch setting. When     A high pressure switch may be provided on the
               evaporator  loads  are  low  it  works  more  like  a  control  condenser in systems with multiple compressors and
               switch. A typical situation would be a windshield de-  condensers that can be isolated. In the event of a failure
               frosting condition in your automobile in the wintertime  of a reversing valve they’re also used on heat pumps.
               because the air conditioning system is operated even if  You might also encounter a high temperature switch
               the temperature inside the vehicle is below the setting  that senses the temperature of the refrigerant in the
               of a thermostat. Of course that assumes you have a ther-  compressor head and shuts down the compressor if that
               mostat to control your automobile air-conditioning.  temperature gets too high. Low system pressure, loss of
                    In larger systems a second low pressure switch  lubrication, or loss of refrigerant flow through the com-
               may be included, called a “low-low” or “limit” switch  pressor could produce high head temperatures without
               and that switch would require manually resetting it to  a high head pressure.
               restore system operation.                                Low oil pressure switches are provided on almost
                    Operation of the low-pressure switch when a sys-  all large compressors. They are occasionally incorporat-
               tem is not maintaining the set temperature is indicative  ed with the combination high and low refrigerant pres-
               of insufficient refrigerant. Checking you should find that  sure switches into one assembly. Equipment such as re-
               evaporator pressure remains low in the system while  ciprocating compressors may have an integral oil pump