Page 186 - Boiler_Operators_Handbook,_Second_Edition
P. 186

Refrigeration & AC                                                                                  171

               that builds up pressure after the compressor starts just  ically  differential  pressure  switches  that  measure  the
               like your automobile. In that case provision includes a  pressure at the inlet and outlet of the heat exchanger and
               contact that bypasses the low oil pressure switch for a  open contacts to shut down the compressor whenever
               few seconds during startup. If you have a compressor  the  water  flow  is  so  low  that  there  is  a  minimal  pres-
               that starts then stops almost immediately check the oil  sure drop. Their operation should be tested annually by
               level again. Do not repeatedly try to start a compressor  closing down on the outlet valves of the condenser and/
               that will not continue to run because bearing damage  or evaporator water circuits and attempting to start the
               can occur. Since refrigerant flow cools the motor and in-  compressor. An established number of turns open for
               rush current heats up the windings during starting you  each valve (degrees, percent, or notches on a butterfly
               should give it a chance to cool off. During annual inspec-  valve) should be determined and included in your SOPs
               tion simply lifting a wire from the bypass circuit should  as starting points. You should be able to use a test light
               prove to prevent the compressor operating. If the com-  at the control panel terminals to detect switch operation
               pressor is fitted with an oil pressure gauge make it a point  when the equipment has both switches.  You can then
               to observe the switch operation and record the pressure  gradually open the outlet valve and note when the first
               at which the contacts close. Note also that oil pressure  switch in the circuit closes, record the inlet and outlet
               switches are actually differential pressure switches that  water pressures then do the same thing for the other.
               compare the oil pressure to the suction pressure (typical-  Using  a  test  light  is  preferable  to  testing  that  requires
               ly in the compressor crankcase) because the flow of oil is  frequent starts of a large compressor but you should still
               determined by that differential.                     confirm that the compressor can’t start when one or both
                    Large compressors can also have high and low  of the switches are actuated by low flow.
               oil temperature switches. The oil temperature switches   A low temperature switch is normally provided
               will prevent compressor operation if the oil tempera-  in any evaporator used to chill water to prevent freez-
               ture is too high or low. Don’t confuse an oil temperature  ing of the water. Even though water flow is maintained
               switch that controls the heater with a high oil tempera-  through  the  evaporator,  a  flow  imbalance  created  by
               ture switch, especially if you decide to set the switch by  foreign substances or associated with the piping con-
               markings on the switch.                              nections to the evaporator can reduce flow sufficiently
                    You  may  be  wondering  if  the  compressor  could  that ice could form in one or more tubes. The result is
               continue to operate completely unloaded. What you’ll  similar to what is shown in Figure 5-30. The thermowell
               discover is that unloading is never 100% complete. Ei-  for the switch is typically inserted into the refrigerant
               ther the compressor is set up with one or two of the cyl-  space to sense the refrigerant temperature which, being
               inders always in operation or throttling devices like the  at saturation, should be consistent throughout the evap-
               adjustable plug of a screw compressor doesn’t unload  orator. During each annual inspection of an evaporator
               everything and the inlet vanes of a centrifugal compres-  containing water the operation of the low temperature
               sor simply leak. Remember that most motors are cooled  switch should be confirmed by removing the sensing el-
               by refrigerant flow; therefore every compressor should  ement (normally a bulb in a thermowell at the bottom)
               be protected by high and low pressure switches and a  and inserting that bulb in a glass of ice water. After a few
               flow switch wouldn’t hurt.                           minutes in that condition you should not be able to start
                    Testing of high and low pressure switches should
               be performed on an annual basis. On individual com-
               pressors throttling the suction and discharge valves
               while observing suction and discharge pressures on
               your  gauge  set  should  serve  to  confirm  operation. As
               with  other  operating  limits  you  should  record  actual
               values whenever possible in the log where you describe
               the testing. Be certain you’ve restored normal valve po-
               sitions and any other  alterations  suggested  for  testing
               by the instruction manual before leaving the equipment
               even if the switches are shown not to work.
                    Water flow switches are used to prevent operation
               of  the  compressor  whenever  water  flow  through  the
               condenser or evaporator is not proven. These are typ-
                                                                           Figure 5-30. Chiller tube after freezing
   181   182   183   184   185   186   187   188   189   190   191