Page 402 - Boiler_Operators_Handbook,_Second_Edition
P. 402

Controls                                                                                            387


               ity. That requires a system that can stop and start each
               boiler as needed and may include modulating controls
               that fire the boilers at different rates. Several methods
               using complex arrangements of linkage, modulating
               motors that operate off another pressure control switch
               connected to the common steam header and powered by
               a shaft which in turn controlled switches and multiple
               electric coils like the one in a pressuretrol were provided
               and you may run into one of them.
                    Okay, I can’t explain it in one sentence and that
               was part of their problem. The principles described for
               a single burner control apply to them but they required
               a lot of maintenance and are, for the most part, replaced
                                                                   Figure 11-21. Settings for automatic three boiler control
               by modern digital controllers that simulate their func-
               tions. If you have one of those, read that instruction
               manual several times and ensure yourself that you have  boiler you just shut down will not generate so much
               an understanding of what it’s supposed to do before you  steam that the pressure rise associated with that steam
               start making adjustments. Then watch what happens  generation trips another boiler.
               when you make adjustments because they may not do        The difference in start (cycle on) settings has to
               what you understood they should do. As of the writ-  be sufficient to allow for the pressure drop that will oc-
               ing of this book there is no national standard applied to  cur while the boiler just started is purging and lighting
               those devices so their descriptions, labels, and settings  off. Figure 11-21 also shows how you can change the
               vary considerably. Another problem is the people that  modulating range. You’ll notice that the setup requires a
               write their instructions and label the panels may have  considerable swing in pressure to satisfy all the criteria.
               completely different or erroneous perceptions of what  If you want to change the order in which the boilers op-
               gain, reset, and other control terms are. They will do a  erate you have to change all the switch and pressuretrol
               good job of controlling your boilers if you buy the right  settings, a lot of work. So it’s much better to have one of
               one and apply it properly.                           those digital controllers to do it all.
                    If you have multiple boilers, need more than one     Many plants have lead-lag controls as part of the
               in operation to serve all the loads, can’t be there to  package for controlling their boilers. The adjustment
               make a decision regarding when to start or stop another  of settings in Figure 11-21 provides a form of lead-lag
               boiler, and your boss won’t put up the cash to buy one  control because it varies the number of operating boil-
               of those modern controllers you’ll have to make do with  ers, allowing Boiler 1 to carry the load until it can’t
               the equipment you have. There’s no reason to change  then bringing on Boiler 2 and finally Boiler 3 to handle
               modulating control settings on the boilers unless you  the maximum loads. All the boilers modulate together.
               have limited turndown (two to one or less) or you have  Lead-lag controllers were designed to accomplish it in a
               adjusted turndown to the degree that you’re very inef-  slightly different manner. They would run the first boiler
               ficient at low fire.                                 up to high fire and leave it there after starting the second
                    That, by the way, is a normal thing to do. Boiler op-  boiler which would modulate to carry the load until the
               erators don’t normally like to see a boiler shutting down  load exceed the capacity of two boilers when the third
               regularly. Creating load and other unwise operations are  would start. Those controllers resolved a problem with
               not the proper way to deal with it though.           the scheme of Figure 11-21 which provided different re-
                    You achieve multiple boiler control by setting your  sponses to load changes depending on how many boil-
               operating pressure switches within the range you would  ers were on line. The lead-lag controller always had only
               use for one boiler. It’s easier to talk in terms of start and  one boiler responding to load changes, the others were
               stop pressures where the stop pressure is the setting of  either on at high fire, or off. One controller was actually
               the boiler pressure control switch and the start pressure  capable of controlling as many as ten boilers.
               is the switch setting less the differential. Figure 11-21     High pressure boiler plants can operate with the
               shows the start and stop settings for three boilers to  same simple modulating control we just reviewed as
               achieve automatic control. The difference between stop  long as there is no problem with the swinging pressure.
               settings has to be enough that the residual energy in a  Once a plant is large enough that someone installs a
   397   398   399   400   401   402   403   404   405   406   407