Controls                                                                                            385


               wise operator should know that he can improve the  above that setting.
               quality of his operation by adjusting that switch. It has     Before we get off the subject of setting the pressure
               two adjustments; one is the pressure at which it opens  control switch there’s a question of where we set the
               its contacts as the pressure increases to stop operation.  stop pressure, the main setting of the pressure control
               The  other  adjustment  is  the  differential  which  is  the  switch. Many operators are instructed to set it as low as
               difference between the contact opening pressure and  possible because that makes the steam and water tem-
               the pressure when the contacts will close again. Well,  perature lower to cool flue gases more and reduce stack
               to be honest the setting could be the pressure it closes  losses. I will contradict that theory because the small
               at and the differential determines when it opens; there  savings in lower stack temperature will be lost with
               are both types.                                      more frequent cycling of the boiler. Set the switch as
                    Set (stop) pressure less differential equals start  high as it can go and still prevent operation of the high
               pressure. Many operators think they should set the dif-  steam pressure switch (see burner management) and it’s
               ferential as low as possible so the pressure won’t swing  for two reasons. One, the larger the spread the longer the
               as much. The result is an increased cycling of the boiler  run time for a boiler when it’s cycling and two, the more
               and lower efficiency (see cycling efficiency). To get the  room you have for continuous operation.
               best performance out of your boiler you should establish     Now we can talk about modulating controls and
               the widest possible operating range.                 the most common of those is a simple electrical propor-
                    For a simple on-off boiler operation your operating  tional control system. A pressuretrol (trademarked name
               range is the differential setting of that switch and the dif-  of Honeywell) connects to the steam space in the boiler
               ferential should be set as large as you can tolerate. You  and consists of a diaphragm or bellows connected to me-
               should find that you can set it larger in the summer than  chanical linkage that adjusts the position of a wiper on
               you can in the winter. The boiler will not start as often.  a coil of wire. The coil has a constant electrical voltage
               It will run longer on each operation but that reduces  across it supplied by a transformer. Voltage at any point
               the frequency of starts so there’s less of them for higher  on the coil is proportional to the position along the coil
               overall operating efficiency and less wear and tear.  because the wire has a constant resistance. A matching
                    The next obvious question is “how do you know  coil is provided in the modulating motor that changes
               how low you can go?” You need enough pressure so all  the firing rate of the boiler.
               the heating equipment in the facility your boiler is serv-     The wipers are not exactly like an automobile
               ing operates properly. Frequently it’s the one that’s the  windshield wiper but they operate similarly, swinging
               longest piping distance from the boiler but sometimes  so they touch the coil at any point from one end to the
               it’s equipment at a shorter piping distance but the pres-  other. A schematic of the system is shown in Figure 11-
               sure drop to that one is higher or it is not as oversized  19. When the steam pressure changes it moves the wiper
               as everything else. The best way to determine it is to  along the coil in the pressuretrol. The voltage between
               gradually drop the lowest pressure (increase switch dif-  ground and the wiper in the pressuretrol will change
               ferential) until someone complains then raise it a bit.  which produces an electrical current through the wiper
                    If you can wander the facility you can read pres-  to the balancing relay and the wiper on the coil in the
               sure gauges and find it. Unless the equipment operates  modulating motor. The balancing relay is upset by the
               at full capacity summer and winter and it has its own  current when the two coils don’t match so it makes one
               steam piping from the boiler plant you can do the same  of the electrical contacts which drives the modulating
               thing in the summer. Summer loads are usually lower  motor.
               than winter loads so piping pressure drops are less and     The direction of the motor is determined by the
               steam demand on the equipment is less so you can drop  voltage imbalance so it runs in a direction that moves
               the pressure a little more at the boiler.            its wiper until it is at the same position as the wiper in
                    A typical heating plant with a switch setting of  the pressuretrol. When the two wipers are in the same
               12 psig can usually operate well in the summer with  position the voltage is the same and no current will flow
               pressures lower than the maximum differential adjust-  through the balancing relay so it centers to stop the mo-
               ment of the switch. I’ve seen plants that operate as low  tor operation. The system rotates the modulating motor
               as 2 psig; however, they had to install a special switch  proportional to steam pressure so it is basically a pro-
               arrangement to get that spread. There’s a caution here  portional controller.
               that is covered more later. Don’t allow the starting     The pressuretrol has two settings just like the
               pressure  to  go  so  low  that  the  boiler  will  modulate  pressure control switch. One establishes the center of