Page 401 - Boiler_Operators_Handbook,_Second_Edition
P. 401

386                                                                               Boiler Operator’s Handbook








































                                        Figure 11-19. Pressuretrol—modulating motor schematic

               the operating range (the steam pressure that will center  to the minimum differential for smooth operation you
               the wiper in the middle of the coil) and the other is the  adjust the differential of the pressure control switch and
               differential which is the change in steam pressure neces-  the setting of the pressuretrol to establish an operating
               sary to drive the wiper from one end of the coil to the  range as depicted in Figure 11-20. In many plants you
               other. You tune it like any proportional controller, reduc-  will find that you can allow some of the differential of
               ing the differential until the operation becomes erratic  the pressuretrol to fall below the minimum operating
               then increase it until it operates smoothly.         pressure because the boiler doesn’t have to modulate to
                    The setting of the center of the operating range of a  high fire to handle the maximum summer load.
               pressuretrol should always be such that the entire oper-     Heating boiler plants may have more than one
               ating range is below the start pressure of the operating  boiler and a need to control operations where two or
               pressure switch. How far below? Enough so the steam  more boilers are required to serve the needs of the facil-
               pressure after the boiler has started and purged at a load
               equal to low fire is slightly higher than the top of the
               operating range of the pressuretrol.
                    When a boiler is cycling on and off the steam re-
               quirement is less than the boiler produces at low fire. At
               those loads the boiler shouldn’t be modulating because
               that increases the input during the firing cycle to shorten
               it and increase cycles. (See cycling efficiency)
                    If all you have is an operating pressure switch
               it’s manufactured switch differential is your operating
               range. When you also have modulating controls your
               operating range is from the stop setting of the pressure
               control switch to the pressure that generates the maxi-
               mum firing rate.
                    After you have tuned your modulating control  Figure 11-20. Range of control, modulating and on-off