Page 403 - Boiler_Operators_Handbook,_Second_Edition
P. 403

388                                                                               Boiler Operator’s Handbook


               steam flow recorder that will change. Normally steam  on line in automatic.
               flow recorders require a constant pressure for accuracy     Modern digital controllers can use digital (on or
               (see boiler plant instrumentation).                  off) inputs to determine which boilers are in automatic
                    When we want to keep producing steam at the same  and calculate what the response will be to a control-
               pressure we need an integral controller. In the early days  ler action so a good digital control system shouldn’t
               of controls one of those controllers was an expensive  be affected by the number of boilers in automatic or
               item so we chose to use one to control all the boilers in  what size they are. The need for that degree of control
               a plant and called it the plant master pressure controller.  sophistication isn’t enough to justify a full explanation
               It sensed the pressure in the common steam header so  in this book. If you’re constantly changing the number
               it wouldn’t be affected by shutting a boiler down and it  or combined capacity of boilers operating on automatic
               was close enough to the steam flow elements that it main-  control and find the response of the master is never that
               tained a reasonably constant pressure at them for accu-  good, there is a solution for it.
               racy in recording. Those rules still apply today but lower
               costs for instruments and controls have made it possible
               to have a controller at every boiler if desired.     FLUID TEMPERATURE MAINTENANCE
                    A plant master pressure controller produces an
               output signal that is used by each set of boiler controls to     Controls for heating fluids require special consid-
               adjust their firing rate so they produce steam to satisfy  eration that’s not necessary for pressure controls. The
               the requirements of the facility while maintaining the  largest single problem is making sure that the device that
               steam pressure in the header at the setpoint. We’ll be  senses the temperature you are using as a process vari-
               discussing the several types of boiler firing rate control  able is representative of the heat flow you are really con-
               systems later but they all change the flow of steam out  trolling. Always be aware that the sensor may be shielded
               of their boiler proportional to the change in the plant  by such things as air trapped above the fluid or scale or
               master signal.                                       other material coating the sensor so it can’t detect the
                    You should always tune your plant master with  temperature properly. It may be necessary to locate the
               the normal number of boilers on automatic. Most plants  sensor where it can’t detect changes in temperature when
               with multiple boilers in service and a plant master run  flow is interrupted; additional sensors and controls (like
               one boiler on automatic and the rest on hand so the plant  a flow switch) may be necessary to prevent hazardous
               master will operate properly regardless of the number of  operation under those circumstances.
               boilers in operation. Note that this works only when all     This chapter is dedicated to boiler plant controls,
               the boilers are the same size. If that’s the case and you  particularly hot water boilers for hydronic heating and
               try operating two boilers on automatic you’ll find the  similar applications. The control of boilers for service
               pressure will jump around a bit when there’s a change  water heating (domestic hot water) is described in the
               in the steam load.                                   chapter on water heating.
                    Under those conditions the two boilers change       Most hot water boilers are supplied with a pro-
               their steam output but the master controller expected  portional control similar to that described for steam
               the change in output to alter the steam flow the same as  boilers. The only difference is the temperature control
               the output of one boiler. With two boilers in automatic  switch and modulating controller sense boiler water
               the response to a controller action is doubled. If you run  temperature, not pressure. In many hydronic systems
               two boilers on automatic most of the time and one on oc-  the quantity of water in the boiler is large enough that it
               casion it’s better to tune the master for two boiler opera-  can operate much like a steam boiler, using temperature
               tion and live with the slower response when one boiler  control instead of pressure. Simply convert the pres-
               is on. Plants with boilers of different sizes will also see a  sure values in the previous figures to the corresponding
               different response out of the plant master.          steam saturation temperature from the steam table in
                    Prior to the days of digital controls it wasn’t practi-  Apprndix A and you have it.
               cal to deal with that situation in the controls, the plant     The decisions for setting the start, stop and modu-
               operator had to adjust the tuning of the master control-  lating range for fluid temperature control are based on
               ler if the operation was erratic. Some plants added de-  several considerations. The fluid has to be hot enough
               rivative control to help account for it. I created a number  when it reaches the using equipment to transfer all the
               of complicated logic systems that adjusted the gain of  heat required. The fluid cannot be so cold that acids in
               the master controller according to the number of boilers  the boiler flue gas condense on the boiler surfaces and
   398   399   400   401   402   403   404   405   406   407   408