Page 433 - Boiler_Operators_Handbook,_Second_Edition
P. 433

418                                                                               Boiler Operator’s Handbook


                    Also don’t expect oxygen trim to be a cure all.  per fire with all the stove air inlets shut to heat up the
               There is a definite lag in time between the change of an  stack before starting a wood fire.
               air to fuel ratio on a burner and the appearance at the     The air that is pulled into the draft hood from the
               analyzer cell of a gas sample that is the result of that  room goes up the stack. It cools the stack gases which
               change. If the controls aren’t aligned properly to main-  lowers the natural draft until there isn’t a significant dif-
               tain an air to fuel ratio with load changes don’t expect  ference between the pressure in the room and the pres-
               the oxygen trim controls to correct that. If you see the  sure under the hood. Since the boiler outlet is under the
               trim controller output change with load that’s what it’s  hood the pressure at the outlet and the boiler inlet dif-
               trying to do. You should also be aware that the oxygen  fers by the natural draft through the boiler. If the hood
               measured at the analyzers didn’t necessarily come  wasn’t there the pressure at the boiler outlet could vary
               through the burners; this is particularly true on induced  so much that it could blow out the fire, as on cold days,
               draft and balanced draft boilers where the furnace and  or be so high that you wouldn’t get enough air for clean
               boiler passes are at a lower pressure than atmospheric  combustion. That draft hood stabilizes a fixed fire opera-
               and air can leak in at several points after the burners.  tion to ensure maintenance of the air to fuel ratio.
                                                                        I still have friends asking me about problems with
                                                                    their gas fired appliances and discover that they went
               FIRING RATE CONTROL—CO TRIM
                                                                    a little overboard with one of those insulating blankets
                                                                    that the home stores are pushing. They plugged up the
                    One solution to problems with oxygen analyzers
                                                                    opening to the hood!
               sensing oxygen that didn’t come through the burners is
                                                                        Instead of a draft hood we’ll occasionally use a
               to control based on another parameter. Carbon monox-
                                                                    barometric damper. That’s a single bladed, usually
               ide, the result of incomplete combustion and a gas that is
                                                                    round, pivoted just above its center, damper that sepa-
               always present in some minute quantities in flue gas can
                                                                    rates the boiler room and the stack. These usually have
               be sensed and controlled. The original oxygen analyzer
                                                                    stops on them so the damper will not swing out at the
               problems still hold for analyzing CO and there’s the
                                                                    bottom into the boiler room. As the stack draft increases
               problem of its finite quantity.
                                                                    the difference in boiler room pressure and the stack base
                    We normally control at about 50 parts per million,
                                                                    forces the damper open and cold air from the boiler
               that is 0.005%, a very little amount of gas in the whole
                                                                    room slips into the stack to cool the stack gases and re-
               and hard to measure accurately. Large utility boilers fre-
                                                                    duce the draft. If the draft gets too low the damper closes
               quently use it to resolve the problems with casing and
                                                                    down to restrict the flow of cold boiler room air into the
               ductwork leakage. The operating modes are the same as
                                                                    stack. The stack temperature then increases to raise the
               for oxygen trim. I’ve never installed one but more mod-
                                                                    draft. Those dampers usually have a weight mounted on
               ern analyzers could change all that.
                                                                    a stud to adjust them, by screwing the weight in and out
                                                                    you change the pressure required to open the damper.
               DRAFT CONTROL                                            Barometric dampers or some other means of con-
                                                                    trolling draft is essential on systems with two or more
                    Many small boilers use natural draft and a natural   boilers attached to the same stack. Draft is always a
               means of draft control. The gas fired hot water heater in   balance between the differential pressure produced by
               a house is one. Most use a draft hood, nothing more than   natural draft and the resistance to gas flowing up the
               an open box over the outlet of the boiler. Natural draft   stack. Double the flow of gas, by firing two boilers in-
               up the stack produces a difference in pressure between   stead of one, and the resistance to flow up the stack will
               the bottom of the hood and the rest of the room so the   increase by a factor of four. It’s obvious that the pressure
               space under the hood is negative with respect to the   at the base of the stack will differ considerably so the
               room. You know, and usually check to ensure, that there   flow of combustion air and flue gases through the boil-
               is a negative there by holding a match or lighter near the   ers will too. It’s impossible to maintain air to fuel ratios
               bottom edge of the hood. If there’s a draft, air flowing   in boilers with a common stack unless you have draft or
               from the room into the hood will pull the flame into the   metering controls.
               hood. I check draft on my wood stove before lighting it      Barometric dampers do a fair job but they also
               by holding a flame near the top of the charging door and   require a lot of additional air supplied to the boiler
               open the door a little; the draft almost always pulls the   room. In the winter you have to heat that air or worry
               flame down into the stove. If it doesn’t, I use a newspa-  about freezing some pipes. If you can’t get exhaust air
   428   429   430   431   432   433   434   435   436   437   438