Page 434 - Boiler_Operators_Handbook,_Second_Edition
P. 434

Controls                                                                                            419


               from other sources and there’s a lot needed to control  the required range (less than two inches of water col-
               that draft, other means of draft control, more expensive  umn). The larger diaphragm transmitter costs a lot more
               means, will lower the operating cost and pay for that  than the standard differential pressure transmitter (like
               expensive control.                                   about three to four times as much) so many a plant is
                    In addition to accounting for a variation in flue  fitted with one that saved the contractor a lot of money
               gas flow, draft controls can maintain a parameter in the  but doesn’t work worth a darn. The desired operating
               boiler, such as furnace pressure, a requirement for bal-  point for a furnace pressure is 0.05 to 0.2 inches of water
               anced draft boilers. Many operators believe that’s the  column below the boiler room pressure. Transmitters
               only place you can control the pressure with draft con-  with a wide range, like 50 inches or so, become too un-
               trols but nothing could be further from the truth. If you  stable for good control. Also, at the low pressures we’re
               have two or more boilers capable of pressurized firing  dealing with for draft control any pressure fluctuations
               you can control the draft anywhere between the furnace  due to a noisy fire create a very noisy pressure signal
               and the outlet for individual boiler control.        and considerable filtering is necessary to get a steady
                    If you’re controlling the common draft (at all boiler  output. Frequently the location of a furnace pressure
               outlets) it has to be controlled there or at a central point  sensing connection has to be moved because the selected
               in the breaching where there’s little difference in pres-  spot just happens to be where heavy pressure waves
               sure  as  flows  change.  I  don’t  recommend  a  common  from combustion noise strike it. Of course there’s also
               control because it can fail to prevent operation of all the  the problem of incomplete combustion that can create a
               boilers and it’s very difficult to get the large damper in  noisy signal.
               a common stack to handle all the turndown that’s re-     Once any problems with the furnace pressure sig-
               quired of it.                                        nal are resolved there’s the problem of load changes.
                    Balanced draft boilers require a means of control-  In the old days when controls were expensive we lived
               ling the induced draft fan to keep a constant pressure in  with that unless the boiler loads were constantly chang-
               the furnace, something slightly less than atmospheric  ing more than ten percent or so. When necessary we
               pressure. A typical control loop looks no different than  added cascade control where the output to the boiler
               any other control loop; a transmitter senses furnace  outlet damper became the output of the air flow con-
               pressure and sends a signal to a controller which alters  troller plus or minus the output of the furnace pressure
               its output to an actuator for a boiler outlet damper or a  controller. The summer which combined the air flow
               damper at the inlet or outlet of the induced draft fan. It  controller output and the furnace pressure controller
               can also vary the speed of the induced draft fan.    output also needed a bias spring to subtract fifty percent
                    The control isn’t that simple because there are a  so the furnace pressure controller output would end up
               number of factors that influence it. First the pressure  at mid range just like two element and three element
               in the furnace of the boiler should only be slightly less  feedwater controls. Those draft control systems got
               than the pressure in the boiler room outside the furnace.  tuned with changes in gain applied to the air flow con-
               That way any air that leaks into the furnace and boiler  troller input and the bias to satisfy control requirements
               passes is kept at a minimum. That air is heated to stack  which varied between boiler start-up and operating
               temperature and thrown away just like excess air so it’s  conditions. Modern microprocessor controls can use the
               a loss that should be minimized. The furnace pressure  stack temperature as an input to help compensate for the
               transmitter is really a differential pressure transmit-  variation in conditions.
               ter comparing furnace and boiler room pressure and it     The use of balanced draft allows the boiler manu-
               should have a maximum range of six inches water col-  facturer to use open inspection doors and joints that
               umn and, preferably, have a range of one inch.       aren’t exactly gas tight in furnace construction. The
                    Don’t do like one plant I checked where they  result is there are plenty of places for atmospheric air
               mounted the transmitter in the control panel and sensed  to enter the furnace. I’ve visited many a plant where
               the pressure using draft gage piping. The control panel  the furnace controller setpoint was at two tenths of an
               was in a conditioned room in another building. The  inch negative or more. The leakage at two tenths is three
               boiler pressurized regularly, blowing smoke and soot  times as much as the leakage at five hundredths where
               out into the operating area. Of course it never blew any  the setpoint should be. Operating at five hundredths
               into the remote control room.                        will allow an occasional puff of furnace gases into the
                    The differential that transmitter measures is so low  boiler room, especially during start-up, but will provide
               it needs a large diaphragm to accurately measure it in  far more efficient operation. With modern microproces-
   429   430   431   432   433   434   435   436   437   438   439