Page 429 - Boiler_Operators_Handbook,_Second_Edition
P. 429

414                                                                               Boiler Operator’s Handbook


               equal you switch the standby fuel controller to auto-  performance during that month can be used to predict
               matic and then switch the leading fuel to manual.    situations when less gas could be burned and increase
                    It doesn’t require an instant transfer because the  the current rate so the gas is consumed by the end of
               controller will simply adjust the two fuels in parallel.  the month.
               Control action will not be smooth with both fuels in     Choice fuel firing can also be associated with
               auto because every change in output produces twice the  burning other combinations of fuels including a fuel
               change in flow compared to firing one fuel; don’t leave  produced by a process in your facility. Some of it may
               both fuel controls in automatic unattended. It’s possible  be sold to another facility. That case could involve burn-
               to control two fuels in auto at once but, why? If you’re  ing the excess fuel the other facility does not use. When
               dual fuel firing there are other reasons, not one of which  the other fuel is gas it is handled by pressure control,
               involves auto operation of both fuels to maintain steam  sensing the pressure of the generated gas and varying
               pressure. To complete the transfer you reduce the firing  the flow of gas to your fired equipment to maintain a
               rate of the lead fuel manually until it is at low fire then  constant pressure at the output of the process. It could
               shut it down.                                        also include a variable setpoint for the gas pressure de-
                    There’s nothing preventing you firing both fuels  veloped by the process that generates the gas. When the
               continuously as long as one is in manual control. It’s  other facility uses more of the generated gas the pressure
               convenient for burning down an oil tank while still fir-  will attempt to drop so the controls reduce the amount
               ing natural gas or firing natural gas at the maximum rate  fired in your equipment to maintain the pressure. When
               allowed by your supplier.                            the other facility uses less generated gas the pressure
                    I should have titled this section multi-fuel burning.  will attempt to rise with the result of your burning more.
               I’ve put in a couple of projects where we burned three     So,  what happens  when neither  facility  needs
               fuels simultaneously, gas, oil and a solid fuel. There are  more of the generated gas? Your firing rate controls will
               very few opportunities to do that so I stuck with the  first reduce the firing rate of the main fuel which is the
               “dual fuel” label. Don’t let that prevent you from con-  only one normally controlled to maintain boiler output.
               sidering firing more than two fuels on one burner; just  When the main fuel firing rate is at minimum then the
               keep in mind that only one can be operating on any one  generated gas control is overridden to maintain the
               automatic control signal.                            boiler output, reducing its use in your boiler. If there is
                                                                    still too much the generated gas pressure will increase
                                                                    and a relief valve will send it to a flare to simply burn it
               FIRING RATE CONTROL—CHOICE FUEL FIRING               and waste the energy. You should be able to note this oc-
                                                                    curring (actually production should advise you that it’s
                    It is possible to fire two fuels and have both on  going to happen) and look for ways to use the generated
               automatic control, just different automatic controls.  gas in other equipment to offset purchased fuel cost by
               Modern microprocessor based controls allow dynamic  utilizing all the generated gas that’s possible to use.
               changes in controller gain so a fuel controller could fire     If the production generates a liquid fuel then de-
               oil and gas together. The question is, why would you  viations in supply of the generated fuel can be absorbed
               want to do that? Choice fuel firing is the incorporation  in storage tanks. Automatic control for such applica-
               of additional controls to meet fuel supplier’s criteria.  tions is unusual. Production should be able to tell you
               You could have a system that calculates the rate gas  of any changes they make in production and you can
               should  be  fired  based  on  the  amount  of  gas  you  are  determine an optimum firing rate for the generated fuel
               allowed to burn and the number of hours left in the  based on production data and the level in the storage
               month. The gas glut created by fracking ( a process of  tanks.
               fracturing gas laden rock in the earth that has produced     Burning of waste gases, oils, and solid fuels gener-
               the gas glut) will eventually diminish and this type of  ated by the plant process operations can also require
               firing may return.                                   analysis of the fuel to determine its proper air to fuel
                    It’s easy with computerized control, you input  ratio so it burns cleanly and efficiently. Liquid and solid
               the amount of gas you’re allowed each month and the  fuels can be stored and tested with the ability to adjust
               controls do the rest. There are several parameters that  air fuel ratio before firing it. Gas fuels, on the other hand,
               the control system needs to make a decision about the  are not easily stored. I had questioned one customer, a
               gas firing rate at any time including the need to burn  refinery, with why they didn’t burn gas that was flared
               a minimum amount of fuel oil. Some history of facility  in the boilers and was told the waste gas varied consid-