Page 424 - Boiler_Operators_Handbook,_Second_Edition
P. 424

Controls                                                                                            409


               of the fuel and air controls so a boiler operating on hand  FIRING RATE CONTROL—ADD AIR METERING
               can be trimmed (adjusted by the operators) to reduce
               excess air.                                              The full title of this control logic is parallel posi-
                    A principle disadvantage of parallel positioning  tioning with air metering. The next evolution in control
               controls is variations in response of the actuators, espe-  systems after parallel positioning was to add air flow
               cially for pneumatic actuators, which can produce tem-  metering. Since air flow is influenced by so many factors
               porary upsets in air to fuel ratio during load changes.  it makes sense to measure the air flow and control it. The
               Unlike the jackshaft system there is nothing to prevent  measured air flow provides feedback to the control sys-
               the fuel valve actuator from moving faster than the fan  tem so the air flow controller can adjust the fan damper
               damper actuator or vice versa. They also have all the  actuator  to  produce  a  repeatable  air  flow.  Instead  of
               disadvantages of the jackshaft system with one provi-  simply positioning the fan damper the control system
               sion to help offset the problems with maintaining air to  adjusts the damper until the air flow signal matches the
               fuel ratio, adjustment of the air to fuel ratio.     plant master position signal.
                    By adjusting the resistance in the loop of a system     The decision to measure air flow started the still
               where  the  air  flow  actuator  follows  the  fuel  flow  ac-  standing arguments about where it should be mea-
               tuator the relative position of the two actuators can be  sured. The type of control system and boiler has some
               varied to provide an excess air adjustment. The adjust-  effect on the choice and you should be aware of all the
               ment is a bias type adjustment in most systems but it  variations. Air metering with measurement across the
               does permit running the air to fuel ratio a little tighter  burner windbox to furnace on multiple burner boil-
               if the operating personnel choose to. It also allows the  ers made it possible to compensate for the number of
               operators to compensate for soot accumulation in the  burners in operation. Because each burner throat is one
               boiler, something that’s not easy to do with jackshaft  orifice in the flow path; changing the number of burners
               controls. To help overcome the problems with the in-  doesn’t change the differential measured at the air flow
               dependent actuators the controls can be enhanced to  transmitter when the register on one closes, but it does
               include a leading actuator provision so the fan damper  change the air flow.
               actuator follows the fuel on a decrease in load and the     Measuring the air flow using a differential across
               fuel actuator follows the fan damper actuator on an  the boiler itself is measuring the flue gas flow, not just
               increase in load.                                    air flow, but that’s not a significant variation since the air
                    In addition to problems with response jackshaft  is 93 to 94% of the flue gas. The problem with using the
               and other modes of parallel control can suffer a degra-  boiler is sooting can change the differential relative to
               dation due to hysteresis associated with wear in link-  air flow and other problems like refractory seals break-
               age connecting the devices used to position dampers  ing up can also alter that differential without the opera-
               and valves. To overcome the problems with response  tor being aware of it.
               and hysteresis manufacturers have developed systems      The best measurement is in a suitable metering
               utilizing synchronous actuators which are, for the most  run or venturi between the forced draft fan and burner
               part, mounted directly on the damper or valve shaft.  windbox but most boilers don’t have enough room
               The synchronous motors are basically electric actuators  there for any kind of precision flow measurement. I’ve
               with an integral positioner that responds to a current  always preferred using the inlet of the forced draft fan to
               signal or digital instructions from a controller. I have  measure air flow, provided it’s a single inlet fan. When
               seen these devices operating smoothly and erratically  a boiler is large enough to justify a double inlet fan
               but don’t have enough experience with them at the  then a good metering element between fan and burner
               time of preparing this second edition to judge them one  windbox is justified as well. Many operators don’t un-
               way or the other. I think we all know that a mechanical  derstand fan inlet metering and some even manage to
               device that’s constantly changing position back and  screw it up so I want to explain it well enough that you’ll
               forth isn’t exactly working right  so  don’t accept  one  understand it.
               that’s doing it.                                         Within the boiler room there is air movement but
                    For all practical purposes a parallel positioning  it’s very slow except for right at the inlet of the forced
               control system is set the same way as a jackshaft control.  draft fan or its silencer. In order for the air to accelerate
               You need some way to set the fuel valve to match the air.  from something very close to zero velocity in the boiler
               Normally a parallel positioning system will have cams  room to the speed it needs to get through the fan inlet
               just like a jackshaft system.                        there has to be a difference in pressure between the two