Controls                                                                                            407


               flow through the valve (precise provided the feedwater
               header and steam pressures are near design). The con-
               troller will not see an unexpected response and control
               operation will be smooth. The added benefit is that you
               can always expect a proportional change in flow when
               operating in hand.



               START-UP CONTROL

                    The only type of start-up control that I believe I
               didn’t create in a system is one that’s called “low fire
               hold.” The control consists of an extra pressure or tem-
               perature switch that opens contacts to prevent automatic
               modulation of a burner when the pressure of tempera-
               ture of the boiler is below the switch setting. Once the
               temperature, and temperature can be used even on steam
               boilers, or pressure rises to a level higher than the switch
               setting the automatic controls can operate.
                    What usually follows is a modulating control run-