Page 425 - Boiler_Operators_Handbook,_Second_Edition
P. 425

410                                                                               Boiler Operator’s Handbook


               locations. The fan creates a lower pressure at the fan inlet  the sensing ring.
               by removing the air that enters it and it’s that void created     There’s only one caveat with this method of air
               by the fan removing the air that the room air rushes into.  flow measurement. You have to be certain there’s no
                    The boiler room itself is nothing more than a big  way for the air you’re measuring to go anywhere but to
               pipe that the combustion air flows through; the fan inlet  the burner. I’ve encountered more than one embarrass-
               is just like an orifice. By measuring the static pressure  ing situation where this method measured the air flow
               at the orifice and subtracting it from the pressure in the  but it didn’t all get to the burner. It won’t work if the
               room we get the velocity pressure which tells us how  there’s air leakage, branch ducts, or the like between fan
               fast the air is flowing into the inlet of the fan. There’s one  and burner.
               thing rather nice about this flow measurement, there’s     The original systems were a little lax in producing
               no orifice coefficient because there’s no measurable fric-  a true flow signal. Recall that the pressure drop we mea-
               tion applied to the airstream between the boiler room  sure is proportional to the square of the flow? Some sim-
               and the fan inlet.                                   ply used the differential signal and counted on the screw
                    My standard arrangement for this measurement of  cam type fuel flow control valve for setting the fuel air
               air flow is shown in Figure 11-35 and requires: a ring of  ratio. Others provided a flow signal somewhat related
               half inch tubing forming a circle equal to two thirds of  to actual air flow but still counted on the adjustment of
               the diameter of the inlet; the holes in the ring drilled just  a cam type fuel valve. The problem was developing an
               a little past center to minimize plugging with dust from  output proportional to flow from a differential pressure
               the air; the ring mounted outside any screen or other  signal. Some of the original air flow transmitters used
               obstruction in the fan inlet that could get dirty to vary  cams, others used combinations of springs, and others
               the signal; mounting of the transmitter at least five fan  used the stretching of the diaphragm used to sense the
               inlet diameters from the inlet of the fan and independent  differential.
               of any obstructions that would produce air velocity near     They all gave way to differential pressure trans-
               the high pressure sensing port of the transmitter; a drop  mitters with panel mounted square root extractors until
               leg to prevent dirt entering the high pressure connection  microprocessor based transmitters were developed. If
               of the transmitter; mounting of the transmitter above the  you ever have an opportunity to visit a museum that
               ring so there’s no way condensate can form and collect  displays controls and devices you’ll quickly appreciate
               in the transmitter and sensing piping to block the signal.  the many tricks used to determine the square root of a
               Any condensate that does form will run out the holes in  signal. Modern microprocessor based instruments either
                                                                    calculate the square root right in the transmitter so the
                                                                    output is directly proportional to flow or the square root
                                                                    is calculated after the differential pressure signal is in-
                                                                    put to the controller.
                                                                        An air metering addition to a parallel positioning
                                                                    controller allows tighter control of air to fuel ratio and
                                                                    should permit operation at less than 15% excess air, in
                                                                    the range of 2-1/2 to 3% oxygen in the flue gas and less
                                                                    on single burner boilers.


                                                                    FIRING RATE CONTROL—
                                                                    INFERENTIAL METERING
                                                                        I mentioned the fact that extracting the square root
                                                                    to convert a differential pressure signal to a flow signal
                                                                    was a little difficult. Early inferential metering systems
                                                                    simply avoided the problem by comparing the differ-
                                                                    ential signals. After all, if it’s proportional to the square
                                                                    root for air flow it must be for oil flow or gas flow so just
                                                                    match up the differential signals, right?
                                                                        Well, it does work, there are some differences be-
                     Figure 11-35. Fan inlet flow measuring ring    tween orifice coefficients and other factors that had to be
   420   421   422   423   424   425   426   427   428   429   430