Page 426 - Boiler_Operators_Handbook,_Second_Edition
P. 426

Controls                                                                                            411


               taken into account and most control systems had provi-  windbox to furnace differential to restore the air to fuel
               sions (adjustable cams) to compensate for it so inferen-  ratio again. The only problem came when someone put
               tial control provided many of the features of metered  a burner in service and forgot to open the register.
               control without the expense (and difficulty) of square
               root extracting.
                    They also solved some problems that were prin-  FIRING RATE CONTROL—
               cipally associated with multiple burner boilers. There  STEAM FLOW/AIR FLOW
               were a lot more multiple burner boilers in the middle
                       th
               of the 20  century because they were either converted     Inferring fuel flow by pressure worked fairly well
               from firing coal or designed to be convertible to coal.  for oil and gas but it didn’t help with coal firing. Steam
               Coal fired designs use a reasonably square furnace, not  flow/air flow systems were developed for coal firing
               the long skinny ones we’re used to on most boilers to-  and are basically inferential metering systems because
               day. The shorter furnace required use of multiple burn-  the steam flow could be equated to fuel flow. If the
               ers.                                                 boiler efficiency and steaming conditions were constant
                    Inferential metering is accomplished by consider-  then a fixed relationship between steam flow and fuel
               ing the fuel delivery systems as an orifice with a pres-  flow would exist because the fuel would generate a pro-
               sure drop that can be measured and comparing that  portional amount of steam. The systems eliminated the
               with the air side pressure drop. These systems were only  problems with, or impossibility of, measuring the coal
               applied to oil and gas fired boilers and they used the  flowing to the fire. Coal fired boilers larger than about
               burner header pressure as a variable that equated to fuel  90,000 pph can justify the expense of metering the coal
               flow. After all, the oil burner tip is an orifice or group of  but smaller units still use steam flow/air flow control.
               them and a gas ring or spud has orifices in it, and the     One problem with steam flow/air flow is the lag
               pressure in the furnace (downstream of the orifice) was  in response associated with load changes. If the plant
               relatively close to zero so it is reasonable to treat the  master  output  increases  there  is  a  delay  associated
               burner header pressure as a value of differential.   with the inertia of the boiler. It takes a little time for the
                    Some gas fired systems used gas at such low pres-  higher coal flow rate to heat up the boiler a little more
               sures it was essential to include a furnace pressure in-  and increase steam flow rate. If the system was set up
               put to the measuring device so the changes in furnace  so air flow followed fuel flow the boiler would probably
               pressure didn’t upset the flow signal although they did  smoke on a load increase.
               experience some difficulty with pressure fluctuations     The systems normally use a parallel positioning
               (see draft control).                                 control methodology where plant master changes pro-
                    Modern instruments have erased the cost ad-     duce a proportional change in fuel feed, primary air flow
               vantages of inferential metering systems so you will  (on pulverized coal fired boilers) and combustion air
               see fewer of them. When inferential metering is used  flow and maintain the ratio of fuel and combustion air
               today the differential is treated as a flow signal and the  flow signals with the steam/air flow ratio on a slow reset.
               square root is extracted by the transmitter or controller  Some engineers refer to steam flow/air flow systems as
               to produce a linear flow signal. One of the more serious  parallel positioning with steam flow trim because the
               problems with inferential metering systems was their  steam flow is used to trim the ratio between fuel and air.
               lack  of  linearity.  The  control  response  was  normally     It’s the timing problem that dictates how tight air
               tuned for the high end of the boiler operation and  to fuel ratio can be maintained with a steam flow/air
               swings accepted at low loads.                        flow system. Gas and oil fired systems could actually
                    In dealingx with those multiple burner boilers they  run a little tighter than a system with air flow metering
               had a distinct advantage, even over today’s full meter-  added because changes in fuel input produced a rapid
               ing systems. The fuel flow based on the burner header  change in steam rate. Pulverized coal fired boilers have a
               didn’t account for the number of burners in service and  delay in load changes associated with changes in coal in-
               the differential from windbox to furnace didn’t account  ventory in the pulverizer so they typically operate with
               for the number of registers open. If a burner tripped the  excess air rates around 30%. Stoker fired boilers have a
               control backed down to restore the header pressure, ef-  larger inventory change effect and have to operate closer
               fectively decreasing the flow so the air to fuel ratio at  to 50% excess air to eliminate fuel rich firing conditions
               the other burners was restored. Later the operator could  (and smoking) during load changes.
               close the register and the air control would restore the     Of course you don’t run all boilers at that rate; the
   421   422   423   424   425   426   427   428   429   430   431