Page 432 - Boiler_Operators_Handbook,_Second_Edition
P. 432

Controls                                                                                            417


               should be right at 50% at any firing rate immediately  duced by the offset of the air flow zero.
               after it’s set up.                                       With this method the oxygen trim controller is
                    I can recall many an operator that was confused  limited and it could easily wind up or down to the end
               because the trim controller didn’t seem to be doing any-  of its output range if there was a considerable change in
               thing because only about 10% of its output range influ-  the fuel or some other factor. If the operator notes that
               enced the air to fuel ratio; talk about reset windup! Bias in  condition the first action should be to check the fires to
               the summer is set to 0.95 so the output is anything from  see if their appearance indicates a condition indicated
               0.95 to 1.0 and the air flow transmitter is set for a range  by the analyzer output. If the fires appear normal then
               16.87% higher than the actual differential (8.11% more  the analyzer should be checked for calibration. It’s un-
               flow) at full load at normal operating conditions so the  common to need any more adjustment than that plus or
               output of the multiplier is 100% under those conditions.  minus 5%.
                    Recall that the oxygen content had to increase as     With our experience getting LNG (liquefied natu-
               firing rate decreased because of loss of turbulence? An  ral gas) added to our normal there was no guarantee
               oxygen trim control has to provide for that and it does  that 5% would always be enough. Rather than allow the
               so by introducing a variable set-point that’s fed to the  trim controls more latitude, I added a manual station so
               oxygen controller. Two methods are used, one adjusts  a boiler operator could put another signal on the sum-
               the oxygen set point as a function of firing rate (basically  mer. Giving that input a gain of 0.1 and changing the
               the boiler master signal) and the other adjusts the set  summer’s bias from 95% to 90% allowed the trim control
               point as a function of load using steam flow. I prefer the  a ±5% and the boiler operator ±5%. If the fires indicate
               latter. A boiler needs more excess air during cold starts  the analyzer is right the operator can adjust the manual
               because the fire doesn’t get the benefit of the heat reflect-  air to fuel ratio adjustment (slowly) to restore the trim
               ed back from a hot burner throat and furnace refractory.  controller’s output to 50%.
               Using steam flow to establish a variable oxygen set point     Note that I used a gain on those inputs so the con-
               produces a higher set point for the trim controls while  troller or operator could adjust their respective outputs
               the boiler is warming up. Once steam flow is established  over the full control range, from zero to 100%. A large
               tighter control can be accommodated and the result is  number of trim controls and similar control loops use
               the same as using the master.                        limits that will not allow that. You might be able to ad-
                    The variable set point is generated by a control  just the output from 0 to 100% but the limits only allow
               device called a function generator. A function genera-  it to work from 40% to 60%, the rest of the time nothing
               tor permits a control technician, or a savvy boiler op-  happens. Operators complained to me when they were
               erator, to produce preset outputs at multiple points of  exposed to limits on the output so I modified the control
               input. Some function generators provide for four points  parameters so they got full range. Now they’re happy. A
               while others allow eleven. Its setup is simple with new  control technician shouldn’t set up a control system to
               microprocessor controls because you can set an output  impose limits that don’t make sense.
               for each input by simply entering the input and output     A 2-1/2% swing in air to fuel ratio is not something
               values into the controller. In my early days we had to do  that I would expect to see in the short term so regular
               it with a cam, like on a valve positioner, to produce the  checks and adjustment of the manual ratio adjustment
               desired output. I believe we did a better job back then,  (to restore the trim output to 50%) are not likely to hap-
               even though it took a lot of time and tooling to deter-  pen. Any significant changes should be discussed with
               mine how then cut the cam. Why? Because the cam was  your control technician because it may indicate prob-
               smooth and a function generator that’s set with specific  lems with the controls or (more likely) one of the flow
               points has sharp changes at the points that can introduce  transmitters.
               instability in the control.                              A boiler with a high stack temperature (over 500°F)
                    In addition to the function generator the oxygen  will  benefit  from  oxygen  trim  control.  Low  pressure
               set point generator should include a bias adjustment  heating boilers and boilers with economizers or air
               or independent summer that allows the operator to  heaters have to burn a fair amount of fuel to justify oxy-
               increase the oxygen set-point to accommodate upsets  gen trim. Single burner boilers can be fired with stack
               or unusual fuel conditions and decrease it when the  oxygen content of 1/2 to 1% with a combination of full
               boiler is firing at a fixed rate (manually set) to optimize  metering and oxygen trim but don’t expect much in fuel
               operation under that condition. The result is a set-point  savings from oxygen trim if you have low stack tem-
               that follows the same slope for excess oxygen that’s pro-  peratures.
   427   428   429   430   431   432   433   434   435   436   437