               When the outdoor temperature is swinging from warm  with thermometers. Normally it is a psi per hour rate
               to cold the amount of time the boiler is held at low fire  that you can track. On large boilers it’s not at all uncom-
               is almost proportional to the average heat load, it will  mon to have to stop and start the burners to limit that
               be less as the average temperature drops and the delay  warm-up rate. Most boilers smaller than a quarter of
               before release to modulation will decrease. Unless you  a million pounds of steam per hour can be allowed to
               are always on hand to control the warm-up of a boiler  warm up at the low fire rate.
               you should have low fire hold controls. One final note,     Fixed fire boilers are absorbing the maximum heat
               on some steam boilers where operating pressures are  input every time the boiler is fired so they have to be
               low you might want to use a temperature switch for low  started and stopped to reduce the warm-up rate. If that’s
               fire hold because pressures can swing more significantly  required, other than on initial start-up, the manufacturer
               generating control problems.                         should provide automatic provisions for it.
                    You really don’t want to suddenly switch from       Multiple burner boilers can be warmed up slowly
               light-off  position  to  modulating  because  the  controls  by only operating one, or a portion of the burners. The
               will simply run the burner right up to high fire when it  burners should be switched regularly, according to the
               isn’t necessary. If you’re controlling the boiler manually  manufacturer’s instructions or every fifteen minutes to
               you should allow it to come on line while at low fire.  one half hour so the heating is more uniform. Always
               Then, when it seems to have reached its limit, gradually  start another burner before extinguishing the one it
               increase the firing rate until the load is up to normal op-  replaces so you don’t have to purge the unit. A purge
               erating conditions, then switch to automatic.        is blowing cold air over the metal you just heated to
                    When the boiler is unattended ramping controls  produce a sudden swing in its exposure to temperature.
               function the same way and are recommended for high  That could produce stress cracks in the metal that you
               pressure steam boilers that start and stop automatically.  don’t want to have. A boiler should be limited to the
               They control the rate of change of the firing rate so it  number of starts and full stops it is exposed to. When
               gradually increases at a constant rate (like going up a  the manufacturer recommends limiting stops and starts
               ramp) until it’s at high fire or, more normally, the set pres-  it’s for high pressure boilers with very thick metal that is
               sure is reached and the automatic controls take over. A  more susceptible to damage from stress due to tempera-
               ramping control should only function on the initial tran-  ture variations across its thickness.
               sition from light-off to automatic, or from low fire hold
               to automatic. The transition rate should be adjustable  Full Metering Switch to Automatic
               and you should set it so the rate is as slow as possible to     Simply switching from light-off position to firing
               minimize thermal shock. Pneumatic and microprocessor  rate control, whether it’s manual or automatic, can be
               based systems are described in the section on controls.  rough with a full metering control system. The fuel and
                                                                    air controls are pre-positioned by the interface with the
               Test Safeties                                        Burner Management system and may be lower or higher
                    Never forget that the safety valves are the last line  than the position that produces flow rates acceptable to
               of a defense against a boiler explosion and test them as  the control system. The result is what we call a “bump”
               soon as possible. First, do a lift test on steam and high  as the controls are suddenly allowed to react to the
               temperature hot water boilers when the pressure has ex-  difference and make some rather abrupt, and usually
               ceeded 75% of the set pressure of the valves. Hot water  excessive, changes in valve or damper positions in an
               boiler safeties can usually be tested before firing by ap-  effort to establish the required flows.
               plying city water pressure.                              On almost any pneumatic or electronic (not mi-
                    As soon as possible in the start-up of a new boiler  croprocessor based) controls you can also experience
               run a pop test of steam and high temperature hot water  problems with reset windup, where the controls detect
               boilers. A pop test is described later.              an error and try to correct it, but can’t, so the controller
                                                                    output continues to increase or decrease until it reaches
               Boiler Warm-up                                       zero or maximum possible output. The outputs are out-
                    Your boiler manufacturer should have indicated  side the control signal range (such as 3 to 15 psig where
               a warm-up rate in the instruction manual. A problem  the signal can drop to zero or climb to 18 psig—the stan-
               with it is normally there’s no way for you to determine  dard supply pressure. Similarly a 1 to 5 volts range can
               if you’re actually doing it. If it were critical for tempera-  be a negative voltage and go as high as 12). In either case
               tures below 212°F then the boiler should be equipped  there is no response to controller action until the control