Page 84 - Boiler_Operators_Handbook,_Second_Edition
P. 84

Boiler Plant Operations                                                                              69


               signal winds back into the normal control range.     is ready to go into service. The data should be collected
                    Modern microprocessor based controls have anti-  as soon as possible and, when necessary, before per-
               windup features and procedureless, bumpless transfer  formance testing. The following list is not necessarily
               (manual to auto and vice versa) features that eliminated  complete. You may note certain things about your new
               the problems with earlier pneumatic and electronic con-  boiler that are not indicated or documented and choose
               trols. It’s possible the system designer didn’t properly  to record those as well. The more data you collect the
               configure those features and you can still experience  more likely you will be able to detect problems with the
               bumps on transfers.                                  boiler during its life.
                    A fuel control valve should be positioned at a mini-     Data should be collected at each firing rate (each
               mum (mechanical) stop where fuel flow after ignition is  screw on a jack shaft cam as shown in Figure 2-4 or each
               more than the controller’s set point. If it isn’t, the con-  10% interval of control signal) and include much more
               troller would wind up to maximum output (and it has  than readings of all boiler mounted instruments, pressure
               lots of time to do it before a main flame starts) so the fuel  gauges, thermometers, etc. On steam boilers the drum
               valve would suddenly swing open when the controls are  level using either a signal level, a temporarily mounted
               released to automatic. If the flow is a little higher than  ruler, or simply the number of nuts at the side of the gage
               the controller’s set point, reset windup (in this case it  glass should be recorded. For hot water boilers the water
               would wind down), there’s simply a delay in response.  level in the expansion tank should be recorded even if it
               However, there may not be sufficient time between main  is adjusted automatically. I have seen many new boilers
               flame ignition and transfer to automatic for the controls  supplied without any pressure gauges on the fuel supply
               to wind down and excessive fuel feed could still occur.  system. Despite that you should find that required test
                    If the controls do wind down before transfer they  ports permit connection of a gage to collect that data. This
               will have to recover and once the fuel valve starts to  is especially important when you have multiple boilers
               open it swings open more than it should. To overcome  or other equipment using a fuel gas supply which would
               those strange actions the interface between Burner Man-  prohibit taking fuel meter readings. If the boiler does not
               agement and combustion controls should actually adjust  have a fuel meter I would recommend purchasing one
               the set points to achieve purge and light-off conditions  and installing it right away so that data could be recorded
               so the controls are controlling all the time. The ramping  and collected continually.
               controls should help overcome that problem with reset     Not all boilers are fitted with draft gages but that
               wind-up on light-off. Bumps off low fire and maximum  should not stop you hooking up a manometer, measur-
               fire can occur during normal firing and are discussed in  ing, and recording the draft (sometimes a pressure read-
               the section on controls.                             ing) at the fan discharge, the burner wind box or burner
                                                                    head, in the furnace, at intermediate points within the
               Collect Performence Data                             convection bank (where accessible), the boiler outlet,
                    Among the many things that don’t need a “break  economizer outlet (when equipped with an economiz-
               in period” a boiler should top the list. From the moment  er), the air heater outlet (when equipped with an air
               the first fire lights in the furnace a boiler begins breaking
               down. So, collecting performance data on a new boiler
               as soon as possible is essential. It gives you a record
               of what the boiler was capable of when it was new,
               completely clean, and not broken. While I know some
               examples of where problems with a new boiler had to
               be corrected before it was accepted a boiler is normally
               at its best when it’s new. Should it happen that changes
               have to be made in a new boiler this data should be col-
               lected once the boiler is accepted. This data provides a
               basis for comparison to actual operating conditions dur-
               ing the life of the boiler and is very helpful in detecting
               the source of problems such as inefficient operation.
                    Given some time to think about this since the first
               edition of this book was published I have come up with
               a list of data that should be collected once a new boiler   Figure 2-4. Adjustment screw on control valve
   79   80   81   82   83   84   85   86   87   88   89