Page 89 - Boiler_Operators_Handbook,_Second_Edition
P. 89

74                                                                                Boiler Operator’s Handbook


                    pressure switch should trip before the fire becomes  boiler is taken off line and left to cool.
                    unstable.                                           The final step in a normal boiler start-up is to
                                                                    establish its manual firing rate or place it in automatic
               •    Decrease oil pressure to the burner while watching  control. Since you should still be at low fire, this can
                    the fire, again at minimum fire. The low oil pres-  require increasing the firing rate manually until the
                    sure  switch  should  trip  before  the  fire  becomes  desired firing rate is reached. If you intend to place it in
                    unstable.                                       automatic you should increase the firing rate until you
                                                                    notice that it’s about the same as the same sized boiler
               •    If the oil is heated at the boiler you can check op-  that’s already on automatic before switching to auto.
                    eration of high and low oil temperature switches  Simply throwing the switch to auto isn’t the appropriate
                    (if present) by adjusting the oil temperature while  way to do things because the boiler controls could swing
                    observing the fire. This takes time due to the ther-  for some time before they are stable again.
                    mal inertia of the system so be prepared for that.
                    If the fuel is heated at a common supply point the
                    testing should only be done when you will not in-  EMERGENCY BOILER START-UP
                    terrupt the operation of other boilers.
                                                                        Emergencies come in two forms, instantaneous
                    What happens if the burner doesn’t trip on low  and impending. If you’ve done your job as far as ob-
               water cutoff, flame failure, or high pressure limit? You  serving the equipment is concerned, regardless of who
               secure it, note the failure in the log, and notify your  maintains it, you shouldn’t face too many of either.
               superiors that it isn’t working properly. A boiler with  There are some emergency situations that are beyond
               malfunctioning safety controls should not be placed in  our control, such as power failures, but we should have
               operation.                                           plans for them; right? Instantaneous emergencies in-
                    Open the boiler isolating valve on a heating boiler  volve an immediate shutdown of the plant or an operat-
               when the boiler pressure is reasonably close to the  ing boiler such that you can’t supply steam to the facility
               header pressure. It’s best to open the second stop valve  served by the boiler plant. Impending emergencies are
               on high pressure boilers when the pressure in the boiler  the ones where you know it’s only a matter of time until
               is within twenty pounds of header pressure. The mini-  you can’t supply that steam.
               mal difference in pressure limits steam wire drawing the     Impending emergencies involve things like the
               second stop valve seats and makes it easier to open the  severe squeal of a fan belt or motor bearing on operating
               valve. When there’s a bypass built into, or around, the  equipment that tells you it’s bound to fail very soon. It
               second stop valve you can use it to pressurize the boiler  can also be clouds on the horizon and the sound of thun-
               header. The normal way is to open the non-return valve  der when you know the power is going to fail because
               when ready to put the boiler on line to build up pressure  you never seem to make it through a thunderstorm
               in the boiler header. In either case, always be certain  without a power failure. Natural occurrences from flood
               the free blow drain valve is open and blowing steam to  to excessive heat to deep snow and forest fires seldom
               ensure yourself there’s no condensate in the header that  come without a warning so they should be impending
               would suddenly enter the plant steam header.         emergencies, something you know is coming.
                    After steam is flowing to the header, as indicated     With your disaster plan in mind you can take ap-
               by a steam flow recorder or a drop in boiler pressure as  propriate action. And that’s why you make the plans, so
               the non-return valve lifts, close the free blow drain of a  you don’t have to stop and think about it. The less time
               high pressure boiler.                                you take to act the more time is allowed for warming
                    Once the boiler is “on-line” which means it is de-  up a boiler and other things that you don’t want to rush
               livering heat to the facility, record the fuel and steam or  unless you have to. If you’ve actually rehearsed those
               other output meter readings. It’s one of the little things  disaster plans you will find yourself surprisingly com-
               I ask operators for that I never get an answer to—“how  fortable with what’s going on.
               much fuel does it take to bring that boiler up and onto     Steam may be such a precious commodity in your
               the line?” If yours is one of those plants that change  plant that you maintain a boiler on hot standby. In that
               boilers frequently it may be a very important question  case, start the standby boiler so it can be brought on
               because there’s considerable amount of fuel used to do  line. Once the problem with the boiler that tripped is re-
               that and an associated amount of energy lost when a  solved you can put it on standby or restore it to service.
   84   85   86   87   88   89   90   91   92   93   94