Boiler Plant Operations                                                                              73


               valve at the steam header is closed the free blow drain  low water cutoff tests if it’s necessary to shut the burner
               valve should be open.                                down to control the rate of heating of the boiler.
                    Set firing rate controls to manual and low fire.     Close the boiler vent valves when the pressure is
               Make one quick trip around the boiler to be certain it  up on heating boilers or 25 psig on power boilers. If the
               isn’t open and all valves are in the proper positions  non-return valve on a high pressure boiler is closed,
               before starting it. Open the fuel block valves slowly to  open it so steam will flow to the free blow drain. If the
               ensure you don’t upset fuel supply to operating boil-  second steam stop valve was left open, open the free
               ers. When firing oil, check an oil burner assembly then  blow drain to drain the boiler header and leave the non-
               and insert in the burner. If oil is steam atomized, open  return closed.
               isolating valves to admit steam to the inlet of the burner     Allow the pressure to increase while observing it
               steam shut-off valve. If oil is air atomized, start compres-  closely. The burner should shut down when the operat-
               sor and admit air to the inlet of the burner air shut-off   ing pressure or temperature control setting is reached.
               valve. Check to be certain normal operating fuel supply  Once that operation is proven, test the high pressure or
               pressures have been established. Blow down the gauge  high temperature limit switch by temporarily installing
               glass and water column while observing the water level  a jumper on the terminals of the control switch. The
               in the glass to assure yourself the boiler contains water.  high limit should shut the boiler down before the safety
                    Turn the burner management control on to allow a  valves open or the temperature of a heating boiler ex-
               burner to start. On multiple burner boilers and in older  ceeds 250°F. It should also lock out to prevent continued
               single burner plants it may be necessary to initiate a  operation. Allow the pressure to fall until it is below the
               purge and burner ignition. When the pilot flame is prov-  operating pressure then reset the controls so the burner
               en, gradually open the atomizing steam or atomizing air  can be started again. Remove the jumper from the con-
               shut-off valve at the burner. This ensures that any fuel  trol switch terminals.
               oil that may be transported to the burner by the atomiz-     Once you’ve proven operation of the low water
               ing medium will be exposed immediately to the ignition  cutoff and the boiler pressure or temperature control
               energy of the ignitor and burned at nearly a normal rate.  and limit switches you can run through successive tests
               Opening the valves earlier can inject a slug of oil into the  of each combustion air and fuel limit switch. Proving
               furnace that would subsequently vaporize to produce  the operation of the low combustion air flow switch can
               an explosive mixture in the furnace and ignite when the  produce a condition of flammable mixtures in the boiler
               pilot comes on. Open the fuel shut-off valve, if the atom-  so you must be careful with that one. In some cases you
               izing medium didn’t produce a fire, to start the main  will have to simply adjust the switch setting to simulate
               burner. If the atomizing medium dumped in some fuel  a condition, not the best of tests, but at least you will
               that produced a fire it’s best to repeat the purge. Some-  have done something to ensure it operates. I’ve attended
               times you’re so slow at opening the steam or air valve  testing programs where many of the fuel and air limit
               that you don’t have time to get fuel on. That’s okay, wait  switches didn’t function when the operator thought
               until it has purged again. This is a normal start-up and  they would.
               you aren’t in a hurry.
                    Shortly after the burner has started and is operat-  •   With the firing rate set at minimum fire, reduce
               ing normally, close the burner manual valve. The burner   combustion air flow by slowly sliding a blank over
               management system should detect a flame failure and      the inlet of the forced draft fan while someone
               initiate a boiler shutdown. Only if the boiler shut down,   watches the fire. The minimum air flow switch
               reset the burner management system for another start.    should trip before the fire gets smokey or unstable.
               Open the burner manual valve after the burner manage-    Take care that the blank doesn’t affect the switch
               ment system indicates an ignitor flame is proven. Hav-   sensing the air flow, use another method of reduc-
               ing restored operation, check the low water cutoffs by   ing air if it does.
               blowing each one down and confirming the burner man-
               agement system shuts the boiler down. Do not use any  •   Increase gas pressure to the burner while watching
               bypass push-button while testing the cutoffs at this time,   the fire, again at minimum fire. The high gas pres-
               you want a full operational test. Once the boiler is up and   sure switch should trip before the fire gets smokey.
               operating it may not shut down for months; this is the one
               and only, best and truest time to confirm that the flame  •   Decrease gas pressure to the burner while watch-
               failure and low water safety systems all work. Repeat the   ing the fire, again at minimum fire. The low gas