Boiler Plant Operations                                                                              63


               event the minimum fire pressure regulator fails. You’ll  operation of an ignitor. Most boilers will be equipped
               probably encounter multiple burner boilers without  with a gas-electric ignitor. Small boilers frequently use
               minimum pressure regulators, and experience the dif-  nothing  more  than  an  electric  spark  to  light  the  fire,
               ficulties of operating without them. All multiple burner  that’s because their burner is the size of an ignitor or
               boilers should have them, one for gas, one for oil, for  smaller. You can also run into some with oil-electric
               more reliable operation.                             ignitors and a few with high energy electric ignitors
                    A low fire position is not a certain solution to prob-  and other unique methods. The bulk of boilers use a gas
               lems when lighting off a boiler. Fixed fire boilers light off   electric ignitor and we’ll stick to that mode. Many of
               at full fire so there is no switch or adjustment to be made  you may choose to call an ignitor a “pilot fire” or “pilot
               and they can experience rough light off. A rough lighting  light” but I’ll simply talk about ignitors and you’re free
               is due to creation of a fuel and air mixture that is outside  to use any of those labels.
               the flammable range (see the chapter on fuels) which fi-     Since ignitors use an electric arc to start the gas or
               nally lights when a proper mixture is established.   oil fire it’s appropriate to make certain the flame sensor
                    When firing gas it’s usually because the mixture is  doesn’t think the electric arc is a fire. Begin by closing all
               fuel rich due to gas leaking past a regulator. A quantity  the manual fuel shut-off valves including the ones that
               of gas is trapped between the regulator and safety shut-  supply fuel to the ignitor. Next, go through several par-
               off valves at a higher pressure than normal. When the  tial ignition cycles to see if the spark is detected. What’s
               shut-off valves open the result is a flow of gas larger  an “ignition cycle?” That’s everything you and the
               than normal for a few seconds until that buildup of gas  Burner Management and combustion controls do from
               bleeds off. On oil fired boilers the gun can start empty  starting of the fans to igniting the main fuel on the first
               with fuel mixing with the air in the gun to produce too  burner fired, including a purge.
               lean a mixture. On the next try, if the gun isn’t purged,     On multiple burner boilers we also have a “burner
               the mixture can be fuel rich. A rich or lean condition  ignition cycle” which includes waiting then trying to
               can be created depending on operation of atomizing  light that burner. If the flame scanner “picks up” (the
               medium controls. If the boiler doesn’t have smooth igni-  system indicates the scanner recognizes a flame which
               tion start looking for short term surges or sags in fuel  is probably from another burner) your burner supplier
               pressure and flow when compared to conditions after a  has a problem and you shouldn’t continue to operate the
               stable fire is established.                          boiler until the problem is fixed. Sometimes you can cor-
                    There’s usually a lot of room for low fire variations  rect the difficulty by re-sighting the scanner (adjust it so
               because most boilers have fan dampers that simply can’t  it points in another direction) but if you do you should
               close enough to produce a minimal excess air condition  perform this check regularly to ensure the adjustment
               at low fire. Those dampers leak so badly that low fire  hasn’t failed to prevent sensing a spark as a flame.
               is usually established with the dampers in what could     We also talk about discrimination and it’s very im-
               be considered a closed position and excess air is still  portant in multiple burner boilers. The flame scanner for
               200 to 300%. A good variable speed drive will provide  a burner should not detect the fire of any other burner.
               lower excess air at low fire but the flow usually has to be  If it does, it can improperly indicate the ignitor, or main
               controlled to overcome problems with changes in stack  flame, of its burner is on and allow the fuel valves to
               draft producing significant changes in the air flow.  remain open when, in fact, there’s no fire there. To pre-
                    Remember, it’s always important that low fire be a  vent this, and any false indication of a fire, a Burner
               stable condition. With multiple burner boilers where the  Management system will normally lock out when a
               code limits low fire air flow to 25% of full load air flow  fire is detected that shouldn’t be there. That’s anytime
               that can be difficult because air fuel ratios can change  a flame is detected but the fuel safety shut-off valves
               with number of burner registers open. Set procedures  aren’t energized. Even with a single burner boiler you
               must be established to get the air flowing at the correct  should make sure that works. Slip the scanner out of the
               amount through the burners to be started; and those  burner assembly during the purge period and expose it
               procedures must then be followed religiously.        to a flame, the burner should lock out.
                                                                        For almost all ignitors the trial time is ten seconds.
               Establish an Ignitor                                 We call it the pilot trial for ignition (PTFI). That means
                    With  low  fire  (actually  light-off)  position  deter-  that  ten  seconds  after  the  ignitor  gas  shut-off  valves
               mined it’s time to actually get a flame going in the  open the scanner must detect a  flame to  permit con-
               burner. Except for very small boilers that involves the  tinued operation of the boiler. If the ignitor flame isn’t