62                                                                                Boiler Operator’s Handbook


               It provides a lot of time to think about why the boiler  remove the guns when the boiler is not to be fired and
               tripped or how it did as you continue with the start-up;  you can readily remove them. That way you have some
               valuable time if you use it.                         degree of confidence that fuel can’t possibly get into the
                    I had a few service technicians working for me that  boiler. It’s better for a leak to appear at the front where
               thought it a nuisance and always shortened the purge  you can see or smell it than to quietly create an explosive
               time (remember, all they had to do was spin a knob on  condition inside the boiler. The most expensive boiler ac-
               a timing relay to change it). Their skill and experience  cident to date, a billion dollars worth, was the result of
               allowed them some leeway in breaking the rules and,  leaking fuel. If you can’t break a fitting to show leakage
               luckily for them, they normally got away with nothing  at the front then you should check an idle boiler regularly
               more than a few singed eyebrows when they stretched  when there is (or could be) fuel in the burner piping.
               it too far. You don’t have that skill and experience so     Once  a purge is complete modulating  boilers
               don’t play Russian Roulette with a boiler explosion. Do  should be positioned for light-off. Because most boilers
               a complete purge.                                    light off at low fire we commonly refer to this as the low
                    A purge must be proven before you start timing  fire position, not the light-off position and I will follow
               it and the purge conditions must be proven during the  suit. You should be aware that light-off position and low
               entire purge period. Purge proving is one thing very few  fire do not have to be the same. Once a burner is operat-
               systems do well and you should assure yourself that the  ing it can usually remain stable at firing rates lower than
               system on your new burner really proves a purge air  rates required to achieve a smooth light-off.
               flow exists. I insist on installing a purge air flow prov-     Where loads can require a boiler to operate at very
               ing device that actually measures the air flow but I dis-  low firing rates on occasion, and it’s more desirable to
               covered that can be defeated (see why they fail) so I’m  keep a boiler going, separate minimum (low) fire and
               confident no automatic control system can really prove  light-off positions may be established. In those instances
               the purge air flow.                                  the position switches have to prove the settings are high
                    The boiler operator should be the final authority  enough for ignition as well as low to minimize input
               on purge air flow and ensure the automatic system’s  during light-off.
               acceptance of the condition is correct. On small boilers     Low fire position switches have always proven to
               the typical proof is a fan running and the controls at  be difficult to maintain and set because the low fire is at
               high fire position. As the boiler size increases, a device  the minimum stops described earlier. I’ve never quite
               to monitor flow should be provided and one that mea-  understood why they’re such a problem because the
               sures air flow just like I suggested for combustion air  position proving switch(es) do not have to be set right at
               flow is best. A proven purge is imperative for safe boiler  the minimum position. I do know that many technicians
               operation. Many of the explosions and regular puffing  try to do just that but it’s simply easier than doing the
               I’ve experienced were the result of an inadequate or  more logical thing which is to determine an acceptable
               non-existent purge (see that chapter on why they fail) so  upper limit for light-off and adjust the low fire switch
               don’t be satisfied with anything less and don’t trust the  accordingly. The acceptable upper limit is determined
               sensors entirely.                                    by increasing the firing rate until lightoff gets rough.
                                                                    That’s above the upper limit and you back off it a little.
               Open Fuel Supply, Prove Lightoff Conditions:             There’s plenty of room for switch adjustment on a
                    When you’re satisfied the purge system is working  multiple burner boiler because low fire has to be estab-
               properly you can open manual fuel shut-off valves to  lished by an independent means of control. The mini-
               bring fuel up to the safety shut-off valves. Don’t open  mum stop on the main fuel flow control valve should
               the burner shut-off valves yet. The piping should be  be set so the flow produces a pressure slightly less than
               checked to ensure the fuel is up to the safety shut-off   desired at low fire with one burner in operation. The ad-
               valves and there are no leaks before proceeding. You  ditional flow can then be provided by the minimum fire
               should also perform a leak test of the fuel safety shut-  controls. I always use minimum fire pressure regulators
               off valves (see maintenance) to ensure they’re working  which bypass the main fuel control valve to maintain a
               properly before proceeding. I know, they’re new valves;  certain minimum pressure in the burner header regard-
               but I also know that valves leak, even new ones!     less of the number of burners in operation. Setting the
                    After that final check you can install the oil guns or  main control valve with its minimum stop to produce
               gas guns that you intentionally left out so no fuel could  almost enough flow for one burner helps make it pos-
               get into the boiler. It’s a good habit to get into, always  sible to keep the boiler from losing all burners in the
   72   73   74   75   76   77   78   79   80   81   82