Page 74 - Boiler_Operators_Handbook,_Second_Edition
P. 74

Boiler Plant Operations                                                                              59

































                                                   Figure 2-3. Manometer on slope



               the square of flow so the measurement when you are at  or a specific pressure for a modulating burner. Pressure
               1/4 flow (25%) will be 1/16 of the reading at high fire.  atomizing burners will follow the rules for flow and
               Run your modulating controls down to the bottom to  pressure drop but air and steam atomized burners don’t.
               see if the manometer reading is about 1/16 of what you  If you can’t get the information from the manual use the
               got at high fire. If it isn’t check that manual again; some  pressure that’s half the range of the pressure gauge for
               boilers are only rated for a 2 to 1 turndown so low fire is  fixed fire burners, 1/5 of that for modulating pressure
               50% and the differential pressure reading would be 1/4  atomizing burners, and 1/16 of it for steam or air atom-
               of the high fire value.                              ized burners. Half the gauge is explained in the chapter
                    If you must adjust linkage, and that’s very pos-  on measurements.
               sible, remember to check for any changes to the high fire     Once you’ve established the required oil pressure
               reading after you’ve ensured the controls will stroke (go  for light-off you can set it. Close the fuel oil recirculation
               from high to low and back) without binding any of the  control valve; a globe type valve in the fuel oil return
               linkage. Once you’ve established light-off combustion  line at the boiler. Position the controls at low fire on
               air flow you can set up the fuel or fuels.           modulating boilers. That can be as simple as holding the
                    Setting up fuel oil at low fire should be a snap.  “decrease” push-button on a jackshaft controlled boiler
               The only problems with it could be an improper piping  to several adjustments on a pneumatic control valve.
               design which, among other things, doesn’t include any  Slowly open the fuel oil supply valve while observing
               fuel oil return. As far as I’m concerned if you install a  the burner supply pressure gauge. Slowly is because
               boiler without a fuel oil return line you’re setting it up  you could interrupt the flow of oil to another (operat-
               for a furnace explosion! With a fuel oil return line you  ing) boiler and shut down the plant. (That’s said by a
               can set up your oil conditions without creating a fire.  dummy that did it more than once!) The burner pressure
                    Before opening the oil valves, make sure the oil  should suddenly jump to oil supply pressure because
               atomizer is not in the burner or open a joint at the hose  the recirculating valve is closed and there is no flow
               or tubing to the burner so you know you’re not dump-  through the piping.
               ing oil during this process. Who says the safety shut-off      Now  you  know  why  we  want  to  be  sure  no  oil
               valves don’t leak?                                   is going to the atomizer, if the safety shut-off valve is
                    Once again check the instruction manual, this time  leaking  there will be oil dripping  or spraying out of
               you’re  looking  for  a  burner  oil  pressure  at  light-off.  the burner yoke or the opening we created. Needless
               That’s either operating pressure for a fixed fire burner  to say, if the safety shut-off leaks we stop start-up and
   69   70   71   72   73   74   75   76   77   78   79