Page 76 - Boiler_Operators_Handbook,_Second_Edition
P. 76

Boiler Plant Operations                                                                              61


               which will produce a measurable air flow that can be  windbox and similar parts the inside is mostly air so
               proven. Proof typically consists of a fan motor starter  you can determine its volume by simply measuring the
               interlock contact and an air flow switch.            outside and multiplying length, width and height to get
                    Note that I said air “flow” switch, on many sys-  the volume. Do the same thing for the boiler. The manu-
               tems a simple pressure switch is used and pressure  facturer’s instruction manual will list the weight of the
               doesn’t prove there’s flow. Too often I see boilers with a  boiler empty and flooded so you can calculate the vol-
               simple windbox pressure switch used to prove combus-  ume of water, steam, steel, and refractory then subtract-
               tion air flow. It’s contacts will close when the fan runs  ing that to get the volume of the gas space in the boiler.
               and open when the fan is shut down because a pressure  Divide the dry weight by 500, the approximate weight
               switch simply compares pressure at the point of connec-  of a cubic foot of steel to determine the steel volume and
               tion and atmospheric pressure. If one of those switches  divide the difference between flooded and dry weight
               is giving you difficulty (they seldom do) you can usually  by 62.4 to determine the volume of water; subtract the
               get it to function by closing the burner register. I’m not  results from the outside volume of the boiler. The total
               saying you should do that, you shouldn’t; there’s no air  gives you the volume of the setting.
               flow through the burner when the register is shut… but     For single burner oil and gas fired boilers you can
               the switch is made!                                  use the required combustion air flow rate for full load air
                    I’ve seen many installations where the operators  flow, see the section on fuels. If the boiler fans cannot be
               have pulled similar tricks to get the boiler operating or  operated at full load air flow on a purge determine the
               keep it operating. Air flow should be proven by a means  actual purge air flow rate (as a percent of full load) using
               that’s independent of such conditions and my favorite  the processes described for estimating the minimum air
               method is using the differential pressure across a fixed  flow. For multiple burner and coal fired boilers use 25%
               (not adjustable) resistance somewhere in the air flow  of the full load air flow as a purge rate. Now you have
               stream. I’ll mention some methods later in the book.  a volume in cubic feet and a rate of flow in cubic feet
                                                                    per minute. Divide the volume by the flow rate and you
               Purge the Boiler                                     know how many minutes it takes to displace the volume
                    Once air flow is proven we “purge” the boiler. A  of the setting which is one air change. Multiply that re-
               purge is a constant flow of air through the boiler that  sult by the required number of air changes (4, 5 or 8) to
               must occur long enough to ensure any combustible ma-  determine the purge timing.
               terial is swept out the stack so it can’t be ignited by the     Maybe you aren’t starting a new boiler but you
               starting burner. On an initial start-up some math has to  would like to know what the required timing for your
               be done to determine the purge timing and the flow rate  existing unit is. The means is described and it’s always a
               may have to be established. Your state law and frequent-  good thing to know. For many of you the result is going
               ly insurance company requirements dictate the flow  to be a surprise. The required purge timing is usually a lot
               rate and timing of a purge. These are the more common  longer than what the boiler is originally set up for. I’m the
               requirements: Single burner boilers can be purged at the  only engineer I know that actually performs those calcu-
               maximum combustion air flow rate unless they are coal  lations to determine the required purge timing.
               fired. Multiple burner and coal fired boilers purge air     It wasn’t a big deal in the days of pneumatic timers
               flow requirements vary but the basic rule is 25% of full  where an operator could reach in the panel and read-
               load air flow.                                       ily turn the timer back… most of them did it. When we
                    Single burner fire tube boilers must purge for suf-  started installing microprocessor based (programmable
               ficient time to displace the volume of the setting four  controller) systems near the end of the twentieth century
               times. Single burner water tube boilers must purge for  some of our customers got very excited; the operators
               sufficient time to displace the volume of the setting eight  couldn’t reach into the control system to change the pro-
               times. Multiple burner and coal fired boilers must purge  gram memory and shorten the purge. As a result, they
               for sufficient time to displace the volume of the setting  had some very long purge times to go through after a
               five times and for at least five minutes.            power interruption or any boiler trip. There’s more on
                    So how to calculate the purge air timing? First  this subject in the section on why boilers blow up. Try to
               calculate the volume of the setting. The setting is ev-  live with the legally binding number if you can.
               erything from the point where combustion air enters      Once you’ve done the math, calculated the correct
               enclosed spaces leading to the furnace to the exit of the  purge time and set the controls for it, use the purge to
               stack. For all the fans, ductwork, air heaters, burner  clear the boiler every time before attempting ignition.
   71   72   73   74   75   76   77   78   79   80   81