Page 73 - Boiler_Operators_Handbook,_Second_Edition
P. 73

58                                                                                Boiler Operator’s Handbook


               ing. Whenever possible have means of detecting the level  Every time I’m told something was tested and I ask for
               as the system fills so you will know what’s happening.  the pressure, voltage, resistance, and I don’t get num-
                                                                    bers I doubt it was done. Yesterday I checked on one of
               Fill Systems                                         those general statements and found it was a lie, the tests
                    Fill the system slowly. Whenever possible use by-  hadn’t been done because there’s no way the results
               pass valves even though the filling may be slower than  would meet the requirements.
               desired. The person attending to the valves controlling
               fluid entering the systems should not leave that post  Start Makeup Systems
               and close the valves immediately upon instructions of,     Once  all pressure  testing  is  completed, begin
               or any sounds from, any observer. I must add that the  operation of the systems in an orderly manner. Water
               valve operator should announce at regular intervals af-  softeners, dealkalizers, etc. should be placed in service
               ter closing a fill valve. We once stood around waiting for  to condition water to be fed to a boiler system. Provide
               a boiler to fill for more than three hours when we finally  means to drain water until water suitably conditioned
               checked with the apprentice that was stationed on the  for the boiler is produced. If the installing contractor
               valve. He closed it when someone shouted “hold it” and  was sloppy you’ll find yourself flushing mud, short
               that’s how it had been for three hours.              pieces of welding rod, and lunch bags containing left-
                    Observe vent valves and close them as fluid reach-  overs out of the line and flushing will become a major
               es them. After the system has filled operate the vent  project. I can remember one job where we had to cut
               valves again to bleed off any air that may have been  the pipe caps off the bottom of drip legs to get the large
               trapped and then migrated to the vents. When filling  rocks out.
               systems with compressible gas use testers and bleed
               the system at the high or low points accordingly (high  Establish Light-off Conditions
               points for systems where the fluid is heavier than air,     The combustible range (see fuels) is so narrow that
               low points for fluids lighter than air).             it really is difficult to establish conditions to create a fire
                    Allow the systems to reach supply pressure or  in a furnace. Today’s modern boilers which surround
               controlled pressure slowly while diligently looking for  the fire with (relatively) cold surfaces don’t provide
               leaks. Compressed gases (including air) will expand ex-  heat or reflect it back to help maintain a fire making fir-
               plosively if the container ruptures so your plan should  ing difficult if conditions are not correct. On fixed fire
               provide for small increases in pressure with hold points  boilers (no modulation) check the instructions for any
               at regular intervals to check for leaks and any signs of  measurements that will help you establish the proper air
               distortion of the vessel or piping that could be caused  flow or conditions for the combustion air. On modulat-
               by the pressure. A hold point, by the way, is when you  ing boilers set the air flow at a low fire (minimum fire)
               have reached a certain time or condition in an operation  condition.
               where you planned to hold everything while check-        If there is no other means of determining where
               ing that the procedure is happening as planned and all  to set the air flow I start at maximum on fixed fire units
               safety measures have been taken. In many cases they’re  and 25% on modulating units. Yes, maximum is easy to
               described in the SOP as a hold point.                set and no, 25% isn’t that hard to determine. If you don’t
                    Hydrostatically test each system after it is filled fol-  have a manometer make one by taping some clear tub-
               lowing the procedures described for pressure testing. As  ing to a yardstick (actually that’s a better manometer, I
               with filling there should be a person assigned to control  always have problems with the tubing coming off my
               the pump or valve that is pressurizing the system.   fancy purchased one); leave a loop of tubing hanging
                    Check electrical circuits that are connected to the  off the low end to hold the water. You just need a way to
               systems during hydrostatic tests to ensure the liquid did  measure the air flow and pressure drop across anything
               not introduce an undesirable ground. Check them again  in the flow path is adequate.
               after all test apparatus is removed and normal connec-     Set up your manometer on a ten to one slope (Fig-
               tions reinstated.                                    ure 2-3) so every inch on the ruler is a tenth of an inch
                    Finally, make certain that all the tests performed  in actual pressure. Position the end of the tubing at the
               are documented. A note in the log saying “tested Boiler  inlet of the forced draft fan or air inlet then fill the ma-
               2” isn’t adequate. The documentation should contain  nometer with water until the level is at zero. Run the fan
               values that demonstrate you really did it. The log should  to high fire (maximum) and record the reading on the
               read “Tested Boiler 2 to 226 psig by the boiler gage.”  manometer. Recall that pressure drop is proportional to
   68   69   70   71   72   73   74   75   76   77   78