60                                                                                Boiler Operator’s Handbook


               call the manufacturer. Assuming there are no leaks we  including broken linkage, should establish a low fire
               have now pressure tested the burner piping at operating  condition.
               pressure (or did you actually hydro test it?) and we can     It pays to look at your equipment to see how it will
               continue with the setup. Crack the recirculating control  fail, if linkage comes loose and can fall to open the fuel
               valve then slowly open it until you’ve established light-  control valve add weights so it will close to minimum
               off pressure at the burner piping (after the firing rate  fire instead. The air flow controls should also rest on a
               control valve) then continue slowly opening the supply  mechanical stop at low fire so the dampers never shut,
               valve while adjusting the recirculating control as neces-  unless they leak so much at closed that low fire air flow
               sary to maintain the pressure.                       is still achieved. I’ve run into a few new full metering
                    Nope, you’re not done. Establishing a pressure for  systems where the designer or contractor felt a mechani-
               light-off isn’t that simple. Remember the chapter on flow?  cal  stop  was  unnecessary,  establishing  minimum  fire
               You aren’t so concerned with pressure as you are with  using control signals; of course most of those discoveries
               flow and establishing the pressure doesn’t prove the flow.  were on plants that had experienced a boiler explosion!
               Use the oil flow indication on full metering systems or  I was there to find out why and no low fire stops is usu-
               take two oil meter readings at a set interval to determine  ally one reason.
               gpm to determine the flow; it should be the design flow
               for fixed fire boilers and 20% to 50% (depending on turn-  Fill Boiler and Test Low Water Cutoffs
               down capability) for modulating boilers.                 Before starting a fire in the boiler, fill it with water
                    If there’s no meter I will count quarter-turns of the  to a low level in the gauge glass, about an inch. Make
               recirculating control valve on another identical boiler,  sure the vent valve on the top of the boiler is open so
               match that position and establish light-off pressure by  air can get out to let the water in. When the water is
               adjusting the control valve. Barring any other means of  heated from cold to boiling it will have swelled so much
               setting it I’ll listen to the recirculating control valve and  that the level will rise to over the middle of the glass. In
               set the low fire pressure while the squeal through the re-  unusual boilers it’s sometimes necessary to drain some
               circulating control valve sounds familiar. After you have  water before the boiler reaches operating temperature
               established a final position for the control valve you can  because the boiler has a large volume of water compared
               set the recirculating control valve to produce a pressure  to the room for expansion in the steam drum. You’ll
               that matches operating pressure at low fire for a good  have to drain water to keep it in sight in the glass.
               smooth light-off.                                        From this point on you have to keep an eye on that
                    Since we don’t recirculate gas you can’t guarantee  water level. When the water level is visible in the gauge
               a light-off position by measuring the flow. We can es-  glass it’s time to test the low water cutoff. Proving a low
               tablish the pressure. For fixed fire units it’s a matter of  water cutoff works on a new boiler is doubly important
               setting the pressure regulator. The pressure regulator on  because there are so many ways to defeat those devices.
               a modulating burner should be set for the design supply  The cutoffs should be tested without operating any by-
               pressure. We’ll get light-off pressure refined when we  pass buttons or similar provisions to ensure they oper-
               perform the initial light-off.                       ate properly. Their failure is a primary reason for boiler
                    Light-off pressure is not necessarily low fire but  failures.
               it usually is. Some burners will operate at lower flows     Be sure to test the low water cutoff properly; simu-
               than that required for light-off and your plant may have  late a loss of water due to evaporation by draining the
               operating conditions where it is imperative to establish  water column or cutoff chamber slowly so the water
               a low fire position independent of light-off. If that’s the  level drops gradually to the cutoff setting. If it doesn’t
               case, your control provisions should includes means of  shut the burner controls down, don’t continue the start-
               proving the light-off conditions.                    up until it’s fixed.
                    Low fire is typically the light-off condition on most
               boilers. It’s imperative that the low fire conditions are  Prove Combustion Air Flow
               fixed  and  reliable  because  many  upsetting  situations     After the boiler is filled with water it’s time to start
               could produce unstable fires and explosive conditions  a burner cycle which always begins with establishing
               otherwise. The fuel flow control valves should never  and proving air flow through the burner and furnace.
               shut,  and  I  do  mean  never!  Their  minimum  position  In very small boilers, like your home hot water heater,
               should be set mechanically so something has to break  airflow is a function of combustion and is not proven.
               before they shut. That way any upset in the controls,  In most boilers, however, it amounts to starting a fan
   70   71   72   73   74   75   76   77   78   79   80