102                                                 Boiler Plant and Distribution System Optimization Manual


                or carbon monoxide.                                 •    Consult the boiler operation and mainte-
                                                                         nance manual supplied with the unit for
                SAFETY                                                   details on the combustion control system or
                                                                         methods of varying burner excess air.
                •    Extremely low excess oxygen operation can
                     result in catastrophic results.

                •    Know at all times the impact of the modifi-
                                                                    FINDING THE SMOKE AND CO THRESHOLD
                     cation on fuel flow, air flow and the control
                     system.
                                                                         Once your boiler is in good working order,
                •    Observe boiler instrumentation, stack and      the next major step in improving efficiency and
                     flame conditions while making any changes      reducing emissions is to establish the lowest level
                     engineering personnel or the boiler manu-      of excess oxygen at which the unit can operate
                     facturer.                                      safely and meet clean air laws.



















                                      Figure 9.26—Desirable smoke spot numbers for various fuels




































                                   Figure 9.27—The effect of smoke spot number on soot build up rate